M E M O R A N D U M. NFPA Technical Committee on Health Care Occupancies. Diane Matthews, Project Administrator

Size: px
Start display at page:

Download "M E M O R A N D U M. NFPA Technical Committee on Health Care Occupancies. Diane Matthews, Project Administrator"

Transcription

1 M E M O R A N D U M TO: FROM: NFPA Technical Committee on Health Care Occupancies Diane Matthews, Project Administrator DATE: January 29, 2010 SUBJECT: NFPA 5000 A2011 ROP Letter Ballot Final Results The Final Results of the NFPA 5000 ROP Letter Ballot are as follows: 21 Members Eligible to Vote 21 Ballots Returned Reasons for negative votes, etc. from alternate members are not included unless the ballot from the principal member was not received. All votes were affirmative on all ballot items with the exception of those noted in the attached report. According to the final ballot results, all ballot items received the necessary 2/3 required affirmative votes to pass ballot. Attachment

2 Log #CP1d BLD-HEA Technical Committee on Fundamentals, Revise text to read as follows:. An area of a building separated from the remainder of the building by construction having a fire resistance of at least 1 hour and having all communicating openings properly protected by an assembly having a fire resistance rating of at least 1 hour. [ 2008] This definition is the preferred definition from the NFPA Glossary of Terms. Changing the secondary definition to the preferred definition complies with the Glossary of Terms Project. The BLD-HEA committee agrees with the Committee Statement associated with the BLD-MEA committee's rejection of the proposal: "The proposed definition is incorrect in that the whole building could be a fire area. The proposed definition would cause a hazardous area room protected by fire-rated barriers to be considered a fire area." 1

3 Log #130 BLD-HEA Joshua W. Elvove, Aurora, CO Revise/Add new text to read as follows: Patient Care Non-Sleeping Suite (Health Care Occupancies). See Patient Care Sleeping Suite (Health Care Occupancies). See (New) Non-Patient Care Suite See Patient Care Suite (Health Care and Ambulatory Health Care Occupancies). A series of rooms or spaces or a subdivided room separated from the remainder of the building by walls and doors. Patient Care Non-Sleeping Suite (Health Care and Ambulatory Health Care Occupancies). A suite for treating patients with or without patient beds not intended for overnight sleeping. Patient Care Sleeping Suite (Health Care Occupancies). A suite containing one or more patient beds intended for overnight sleeping. (New) Non-Patient Care Suite (Heath Care and Ambulatory Health Care Occupancies). A suite within a health care or ambulatory health care occupancy that is not intended for treating patients Adding patient care before suite and non-sleeping suite will clarify that these particular suite requirements only apply to health care or ambulatory health care occupancies. Ambulatory health care occupancies were added because suites are referenced in Changing Sleeping Suites to Patient Care Sleeping Suites ( ) will ensure the requirements of et al will not be incorrectly applied to areas where non-(health care) patient sleeping occurs (e.g., on call suites, residential board and care suites, etc.) Changing Non-Sleeping Suites to Patient Care Non-Sleeping Suites ( ) will ensure that the requirements of for Non-Patient Care Suites (e.g., the 200 ft travel distance requirement) are not incorrectly applied to Patient Care Non-Sleeping Suites since a Non-Sleeping Suite is also generally a Non-Patient Care Suite. Adding a new definition for Non-Patient Care Suites ( ) will assist when interpreting the requirements of Renaming suite designations will also require renumbering the placeholder definitions ( , ) since they are in alphabetical order and a new placeholder definition will be necessary for Non-Patient Care Suites. See companion proposal for suites for Chapters 18 & 19 where similar changes are being proposed. Revise as follows: Patient Care Non-Sleeping Suite (Health Care Occupancies). See Patient Care Sleeping Suite (Health Care Occupancies). See Non-Patient Care Suite See Patient Care Suite (Health Care and Ambulatory Health Care Occupancies). A series of rooms or spaces or a subdivided room separated from the remainder of the building by walls and doors. Patient Care Non-Sleeping Suite (Health Care and Ambulatory Health Care Occupancies). A suite for treating patients with or without patient beds not intended for overnight sleeping. Patient Care Sleeping Suite (Health Care Occupancies). A suite containing one or more patient beds intended for overnight sleeping. Non-Patient Care Suite (Heath Care and Ambulatory Health Care Occupancies). A suite within a health care or ambulatory health care occupancy that is not intended for sleeping or treating patients The action does what the submitter but in the last items changes "not intended for treating patients" to "not intended for sleeping or treating patients." The action also editorially removes two occurrences of the label "(New)." Affirmative: 20 Negative: 1 AMBROSE, J.: While I am not against this proposed code change that eliminates the suite requirements of the code from all non-patient care areas on a health care floor/building, there is no substantiation provided to justify that this code change is a valid or safe code change. As currently written in NFPA 5000, the suite provisions of the code applied to all areas on a health care floor/building including non-patient care areas unless that use/area was separated by a 2 hour fire barrier from the health care use. 2

4 k Log #CP750 BLD-HEA Technical Committee on Health Care Occupancies, Revise as follows: Changes of use or occupancy classification shall comply with 4.5.6, unless otherwise permitted by one of the following: (1) A change from a hospital to a nursing home or from a nursing home to a hospital shall not be considered a change in occupancy classification or a change in use. (2) A change from a hospital or nursing home to a limited care facility shall not be considered a change in occupancy classification or a change in use. (3) A change from a hospital or nursing home to an ambulatory health care facility shall not be considered a change in occupancy classification or a change in use. Any building of Type I(442), Type I(332), Type II(222), or Type II(111) construction shall be permitted to include roofing systems involving combustible supports, decking, or roofing, provided that all of the following criteria are met: (1) The roof covering meets Class A requirements in accordance with NFPA 256. (2) The roof is separated from all occupied portions of the building by a noncombustible floor assembly having not less than a 2-hour fire resistance rating that includes not less than 2½ in. (63 mm) of concrete or gypsum fill. (3) Structural elements supporting the 2-hour fire resistance rated floor assembly specified in (2) are required to have only the fire resistance rating of the building. Any building of Type I(442), Type I(332), Type II(222), or Type II(111) construction shall be permitted to include roofing systems involving combustible supports, decking, or roofing, provided that all of the following criteria are met: (1) The roof covering shall meet Class A requirements in accordance with NFPA 256. (2) The roof/ceiling assembly shall be constructed with fire-retardant-treated wood meeting the requirements of this. (3) The roof-ceiling assembly shall have the required fire resistance rating for the type of construction. Locks shall not be permitted on patient sleeping room doors, unless otherwise permitted by one of the following: (1) Key-locking devices that restrict access to the room from the corridor and that are operable only by staff from the corridor side shall be permitted, provided that such devices do not restrict egress from the room. (2) Locks complying with shall be permitted. Doors within a required means of egress shall not be equipped with a latch or lock that requires the use of a tool or key from the egress side, unless otherwise permitted by one of the following: (1) Locks complying with shall be permitted. (2)* Delayed-egress locks complying with shall be permitted. (3)* Access-controlled egress doors complying with shall be permitted. (4) Elevator lobby exit access door locking in accordance with shall be permitted. Doors that are located in the means of egress and are permitted to be locked under other provisions of shall comply with both of the following: (1) Provisions shall be made for the rapid removal of occupants by means of one of the following: (a) Remote control of locks (b) Keying of all locks to keys carried by staff at all times (c) Other such reliable means available to the staff at all times (2) Only one locking device shall be permitted on each door. Aisles, corridors, and ramps required for exit access in a hospital or nursing home shall be not less than 8 ft (2440 mm) in clear and unobstructed width, unless otherwise permitted by one of the following: (1) Where ramps are used as exits, the requirement of shall apply. (2)* Aisles, corridors, and ramps in adjunct areas not intended for the housing, treatment, or use of inpatients shall be not less than 44 in. (1120 mm) in clear and unobstructed width. (3) Where the corridor width is at least 6 ft (1830 mm), projections not more than 6 in. (150 mm) from the corridor wall, above the handrail height, shall be permitted for the installation of hand-rub dispensing units in accordance with

5 (4) Where the corridor width is at least 6 ft (1830 mm), projections shall be permitted in corridors, at both sides of the corridor, as follows: (a) Each projection shall not exceed a depth of 6 in. (150 mm). (b) Each projection shall not exceed a length of 36 in. (915 mm). (c) Each projection shall be positioned not less than 40 in. (1015 mm) above the floor. (d) Each projection shall have a minimum 48 in. (1220 mm) horizontal separation from adjacent projections. (5)* The requirement of shall not apply to exit access within a room or suite of rooms complying with the requirements of Aisles, corridors, and ramps required for exit access in a limited care facility or hospital for psychiatric care shall be not less than 6 ft (1830 mm) in clear and unobstructed width, unless otherwise permitted by one of the following: (1)* Aisles, corridors, and ramps in adjunct areas not intended for the housing, treatment, or use of inpatients shall be not less than 44 in. (1120 mm) in clear and unobstructed width. (2) Where the corridor width is at least 6 ft (1830 mm), projections not exceeding 6 in. (150 mm) from the corridor wall, above the handrail height, shall be permitted for the installation of hand-rub dispensing units in accordance with (3) Where the corridor width is at least 6 ft (1830 mm), projections shall be permitted in corridors, at both sides of the corridor, as follows: (a) Each projection shall not exceed a depth of 6 in. (150 mm). (b) Each projection shall not exceed a length of 36 in. (915 mm). (c) Each projection shall be positioned not less than 40 in. (1015 mm) above the floor. (d) Each projection shall have a minimum 48 in. (1220 mm) horizontal separation from adjacent projections. (4)* The requirement of shall not apply to exit access within a room or suite of rooms complying with the requirements of The requirements of shall not apply where otherwise permitted by one of the following: (1) Unprotected vertical openings in accordance with shall be permitted. (2) The provisions of (1)(a) shall not be permitted to apply to patient sleeping and treatment rooms. (3) Multilevel patient sleeping areas in psychiatric facilities shall be permitted without enclosure protection between levels, provided that all of the following conditions are met: (a) The entire normally occupied area, including all communicating floor levels, is sufficiently open and unobstructed, so that a fire or other dangerous condition in any part is obvious to the occupants or supervisory personnel in the area. (b) Egress capacity is sufficient to provide simultaneously for all the occupants of all communicating levels and areas, with all communicating levels in the same fire area being considered as a single floor area for purposes of determination of required egress capacity. (c) The height between the highest and lowest finished floor levels is not more than 13 ft (3960 mm), with the number of levels permitted to be unrestricted. An approved automatic smoke detection system shall be installed in corridors throughout smoke compartments containing patient sleeping rooms and in spaces open to corridors as permitted in nursing homes by , unless otherwise permitted by one of the following: (1) Corridor systems shall not be required where each patient sleeping room is protected by an approved smoke detection system. (2) Corridor systems shall not be required where patient room doors are equipped with automatic door-closing devices with integral smoke detectors on the room side installed in accordance with their listing, provided that the integral detectors provide occupant notification. Corridors shall be separated from all other areas by partitions complying with through unless otherwise permitted by one of the following: (1) Spaces shall be permitted to be unlimited in area and open to the corridor, provided that all of the following criteria are met: (a) The spaces are not used for patient sleeping rooms, treatment rooms, or hazardous areas. (b) The corridors onto which the spaces open in the same smoke compartment are protected by an electrically supervised automatic smoke detection system in accordance with , or the smoke compartment in which the space is located is protected throughout by quick-response sprinklers. (c) The open space is protected by an electrically supervised automatic smoke detection system in accordance with , or the entire space is arranged and located to allow direct supervision by the facility staff from a nurses' station or similar space. (d) The space does not obstruct access to required exits. (2) Waiting areas shall be permitted to be open to the corridor, provided that all of the following criteria are met: 4

6 (a) The aggregate waiting area in each smoke compartment does not exceed 600 ft2 (55.7 m2). (b) Each area is protected by an electrically supervised automatic smoke detection system in accordance with , or each area is arranged and located to allow direct supervision by the facility staff from a nursing station or similar space. (c) The area does not obstruct access to required exits. (3)* The requirement of shall not apply to spaces for nurses' stations. (4) Gift shops not exceeding 500 ft2 (46.5 m2) shall be permitted to be open to the corridor or lobby. (5) In a limited care facility, group meeting or multipurpose therapeutic spaces shall be permitted to open to the corridor, provided that all of the following criteria are met: (a) The space is not a hazardous area. (b) The space is protected by an electrically supervised automatic smoke detection system in accordance with , or the space is arranged and located to allow direct supervision by the facility staff from the nurses' station or similar location. (c) The area does not obstruct access to required exits. The requirements of through shall not apply to any of the following: (1) Stories that do not contain a health care occupancy and that are located directly above the health care occupancy (2) Areas that do not contain a health care occupancy and that are separated from the health care occupancy by a fire barrier complying with (3) Stories that do not contain health care occupancies and that are more than one story below the health care occupancy (4) Open-air parking structures protected throughout by an approved, electrically supervised automatic sprinkler system in accordance with Section 55.3 Doors in smoke barriers shall meet all of the following criteria: (1) They shall comply with but shall be exempted from (2) They shall be self-closing or automatic-closing in accordance with (3) Clearance under the bottom of smoke barrier doors shall not exceed ¾ in. (19 mm). Where the smoke compartment being modified is not protected throughout by an approved, electrically supervised automatic sprinkler system, corridor walls shall comply with all of the following: (1) They shall have a fire resistance rating of not less than ½ hour. (2) They shall be continuous from the floor to the underside of the floor or roof deck above. (3) They shall resist the passage of smoke. Where the smoke compartment being modified is not protected throughout by an approved, electrically supervised automatic sprinkler system, all of the following shall apply: (1) Doors protecting corridor openings shall be constructed of 1¾ in. (44 mm) thick, solid-bonded core wood or of construction that resists the passage of fire for not less than 20 minutes. (2) Door frames shall be labeled or of steel construction. (3) Existing roller latches demonstrated to keep the door closed against a force of 5 lbf (22 N) shall be permitted. The BLD-HEA committee was directed, by the Technical Correlating Committee, to review its occupancy chapter provisions that are of the list-type format and to revise, as needed, to clearly indicate whether the items in the lists apply to "all of", "one of", or "any of" the items. The revisions shown in the Recommendation field clarify intent. 5

7 l Log #CP756 BLD-HEA Technical Committee on Health Care Occupancies, Revise as follows: Multiple occupancies shall be in accordance with Section 6.2 and Where there are differences in the specific requirements in this chapter and provisions for mixed occupancies or separated occupancies as specified in and 6.2.4, the requirements of this chapter shall apply. (See ) Sections of health care facilities shall be permitted to be classified as other occupancies in accordance with the separated occupancies provisions of and either or Sections of health care facilities shall be permitted to be classified as other occupancies, provided that they meet all of the following conditions: (1) They are not intended to serve health care occupants for purposes of housing, treatment, or customary access by patients incapable of self-preservation. (2) They are separated from areas of health care occupancies by construction having a fire resistance rating of not less than 2 hours. (3) The construction type and supporting construction of the health care occupancy shall be based on the story on which it is located in the building in accordance with the provisions of Chapter 7. (4) The construction type of the areas of the building enclosing the other occupancies shall be based on the applicable provisions of Chapter 7 for the occupancy involved. Ambulatory care facilities, medical clinics, and similar facilities that are contiguous to health care occupancies, but that are primarily intended to provide outpatient services, shall be permitted to be classified as business occupancies or ambulatory health care facilities, provided that the facilities are separated from the health care occupancy by not less than 2-hour fire resistance rated construction and the facility is not intended to provide services simultaneously for four or more inpatients who are litterborne. Renumber through as through Doctors' offices... It is the intent... Clarification. Correlation with related change being made to NFPA 101 via Proposal STEVENS, S.: Wording should be consistent with NFPA and Wording in last sentence should be...simultaneously for four or more patients who are incapable of self preservation. 6

8 m Log #CP757 BLD-HEA Technical Committee on Health Care Occupancies, Revise current as follows: Sections of health care facilities shall be permitted to be classified as other occupancies, provided that they meet all both of the following conditions: (1) They are not intended to serve health care occupants for purposes of housing, treatment, or customary access by patients incapable of self-preservation. (2) They are separated from areas of health care occupancies by construction having a fire resistance rating of not less than 2 hours. (3) The construction type and supporting construction of the health care occupancy is based on the story on which it is located in the building in accordance with the provisions of Chapter 7. (4) The construction type of the areas of the building enclosing the other occupancies shall be based on the applicable provisions of Chapter 7 for the occupancy involved Insert a new before current (and renumber existing paragraphs as needed) to read as follows: Where separated occupancies provisions are used in accordance with either or , the most stringent construction type shall be provided throughout the building unless the 2-hour separation is a vertically-aligned fire barrier wall, and then the construction type shall be determined as follows: (1) The construction type and supporting construction of the health care occupancy shall be based on the story on which it is located in the building, in accordance with the provisions of (2) The construction type of the areas of the building enclosing the other occupancies shall be based on the applicable occupancy chapters of this. Correlation with similar change being made to NFPA 101 via Proposal In the NFPA 101 version, the new references but there is no similar provision in NFPA Thus, the language "unless the 2-hour separation is a vertically-aligned fire barrier wall" was inserted to capture the essence of the requirement from NFPA

9 n Log #CP758 BLD-HEA Technical Committee on Health Care Occupancies, Revise as follows: Contiguous Non-Health Care Occupancies. Ambulatory care facilities, medical clinics, and similar facilities that are contiguous to health care occupancies, but are primarily intended to provide outpatient services, shall be permitted to be classified as business occupancies or ambulatory health care facilities, provided that the facilities are separated from the health care occupancy by not less than 2-hour fire resistance-rated construction and the facility is not intended to provide services simultaneously for four or more inpatients who are litterborne. Ambulatory care facilities, medical clinics, and similar facilities that are contiguous to health care occupancies shall be permitted to be used for diagnostic and treatment services of inpatients who are capable of self-preservation. The use of ambulatory and business occupancies for patients who are capable of self-preservation has been eliminated based on the historical fire record of ambulatory health care facilities and business occupancies serving health care occupants. Diagnosis and treatment facilities are commonly placed in occupancies (ambulatory or business) that would not fall under the hospital provisions of the Code yet continue to provide a fire safe environment. STEVENS, S.: should be consistent with NFPA and Last sentence should read:...simultaneously for four or more patients who are incapable of self preservation Log #171 BLD-HEA Ignatius Kapalczynski, CT Office of State Fire Marshal Add new text to read as follows: (1) Not more than 10 locks need to be unlocked to relocate all occupants from one smoke compartment to an area of refuge (2) Unlocking of all necessary locks shall be accomplished with not more than two separate keys. Proposal establishes lock/key limits to achieve the goals of 18/ and 18/ where a manual locking condition similar to Condition IV is possible in Health Care. This limitation on key locking is taken from the Detention Occupancy. Detention recognizes the need to limit key operations for timely removal of occupants and this proposal places the same limitation on Health care locking which should not be more restrictive or unlimited (1) and (2). The change would have an adverse effect on psychiatric wards, but there is no technical substantiation for such change. 8

10 Log #129 BLD-HEA Joshua W. Elvove, Aurora, CO Revise text to read as follows: Doors that are located in the means of egress and are permitted to be locked under other provisions of shall comply with the following: (1) Provisions shall be made for the rapid removal of occupants by means of one of the following: (a) Remote control of locks from within the locked area (b) Keying of all locks to keys carried by staff at all times (c) Other such reliable means available to the staff at all times As currently written, staff within a locked area may not have the means to unlock a door from within the locked area. This puts staff dangerously at risk. Given this, there needs to be a requirement for staff located within the locked area to unlock the doors without having to rely on personnel located remotely. There is a need for the control room to be located outside the space as the patients must not have access to the unlocking device. Also, a single sleeping room could be considered to be the locked space so as to prevent the controls from being located at the nurses station Log #173 BLD-HEA Ignatius Kapalczynski, CT Office of State Fire Marshal Add new text to read as follows: (x) Egress door locks released by keypad activated codes shall require keypad activation on the ingress side to assure that the programmed code is demonstrated to be known and used at least once prior to entry by any staff entering the secured area. All keypads shall be programmed with the same code throughout any areas where staff movement may occur. Proposal offers a method to confirm that all staff is made aware of the keypad code(s) of the day and that keypads are programmed in a consistent manner. While awaiting documentation of an emergency where keypad codes were not remembered or confused, personal experience suggests that memorizing different changing codes for each nursing unit is particularly difficult for staff which traverses multiple units in the course of their duties and for per diem staff who must memorize numerous codes from the multiple facilities where they may be assigned on a temporary basis. The substantiation is inadequate to verify that staff has been unable to unlock doors where the keypad is only on the inside of the locked unit. To require a key pad on the outside of the locked unit might lead to unnecessary locking of the unit entry which is often left unlocked. 9

11 a Log #CP752 BLD-HEA Technical Committee on Health Care Occupancies, Revise as follows:. The number of means of egress shall be in accordance with Section 7.4. Not less than two exits shall be provided on every story. Not less than two separate exits shall be accessible from every part of every story. Not less than two exits shall be accessible from each smoke compartment, and egress shall be permitted through an adjacent compartment(s) but shall not require return through the compartment of fire origin. An exit is not necessary Correlation with changes being made to NFPA 101. The change is editorial and formatting in nature only. It makes no technical change. 10

12 Log #128 BLD-HEA Joshua W. Elvove, Aurora, CO Revise (A), (B) and (C) as follows:: Occupants of habitable rooms within sleeping suites shall have exit access to one of the following: (1) a corridor complying with without having to pass through more than one intervening room. (2)* a space separated from the suite by a minimum of one hour fire reistance rated construction that is not considered a hazardous area and leads to corridor without having to pass through another intervening room. Occupants of habitable rooms within non-sleeping suites shall have exit access to one of the following: a corridor complying with without having to pass through more than two intervening rooms. )* a space separated from the suite by a minimum of one hour fire reistance rated construction that is not considered a hazardous area and leads to corridor without having to pass through another intervening room. Non-sleeping suites of more than 2500 ft 2 (230 m 2 ) shall have not less than two exit access doors remotely located from each other. One means of egress from the suite shall be directly to Occupants of non-sleeping suites shall have exit access to one of the following: a corridor complying with a space separated from the suite by a minimum of one hour fire reistance rated construction that is not considered a hazardous area and leads to corridor without having to pass through another intervening room. For suites requiring two means of egress, one means of egress from the suite shall be permitted to be into another suite, provided that the separation between the suites complies with the corridor requirements of through Add the following new annex notes: A (A)(2) Examples include another suite, horizontal exit, or another smoke compartment. A (A)(2) Examples include another suite, horizontal exit, or another smoke compartment. A (B)(2) Examples include another suite, horizontal exit, or another smoke compartment. Current text is too restrictive as it mandates at least one means of egress from a suite be into a corridor, when other options (e.g., horizontal exits, smoke compartments, suites separated by fire resistance rated construction, are equally as safe. I have run into many situations where a suite has no access to a corridor, but has access to a stair and two additional suites that are separated from all adjacent suites by fire resistance rated construction, yet this configuration, regardless of the safeguards provided, does not meet the LSC. Proposed text aims to provide additional options to the traditional corridor. The committee is uncertain what form such spaces can take. What limitations are intended? Does the space need to be supervised? For small spaces under 2500 sq ft, the change would result in no requirement for direct corridor access such that it would be OK to route the one-and-only way out through an adjacent space. The submitter does not speak to this effect that the revised wording creates. How can such change be substantiated.? Yes, travel to a stair qualifies as reaching an exit, but stairs do not provide patients (think: difficult to move, especially vertically on stairs) with a helpful route as contrasted with the current requirements that facilitate the horizontal movement to another smoke compartment or another part of the floor. Affirmative: 20 Negative: 1 STEVENS, S.: It is incorrect to presume all patients are difficult to move. Text should allow options and leave it to facility and staff to use best option. O'CONNOR, D.: The proponent makes a good case for alternative options. The Committee should continue to explore the concepts proposed and work towards a solution in the ROC phase. 11

13 Log #127 BLD-HEA Joshua W. Elvove, Aurora, CO Revise , , , and as follows: Change Sleeping Suite to Patient Care Sleeping Suites Revise , , , and as follows:: Change Non-Sleeping Suite to Patient Care Non-Sleeping Suites Changing Sleeping Suites to Patient Care Sleeping Suites will ensure the requirements of et al will not be incorrectly applied to areas where non-(health care) patient sleeping occurs (e.g., on call suites, residential board and care suites, etc.) Changing Non-Sleeping Suite to Patient Care Non-Sleeping Suites will ensure that the requirements of for Non-Patient Care Suites (e.g., the 200 ft travel distance requirement) are not incorrectly applied to Patient Care Non-Sleeping Suites since a Non-Sleeping Suite is also generally a Non-Patient Care Suite. Note: also see companion proposal for revising suite definitions Log #174 BLD-HEA Ignatius Kapalczynski, CT Office of State Fire Marshal DELETE section. Proposal restores self closers on patient room doors. Prior Technical Committee statement places much greater faith in staff actions than actual incidents have documented. Staff supervision as addressed by the required emergency plan is adequate to assure that doors will be closed when needed, is not supported by staff actions in actual multiple fatality fires. Staff actions to affect rescue in the room of fire origin have resulted in delays or failure of other patient room doors being closed in timely manner and allowed the migration of smoke and heat beyond the room of origin. The General Accounting Office report following the 2003 Hartford, CT and Nashville, TN multiple fatality fires stated that staff training was not dependably effective. Proposal continues to be based on direct personal observations and research of what worked and what did not work at several health care facility fires. The BLD-HEA committee notes that the submitter probably intended to address and not The fires cited involved non-sprinklered nursing homes. 12

14 a Log #CP754 BLD-HEA Technical Committee on Health Care Occupancies, Revise as follows: Alcohol-based hand-rub dispensers shall be protected in accordance with Section 8.15 and Chapter 34, unless all of the following conditions are met: (1) Where dispensers are installed in a corridor, the corridor shall have a minimum width of 6 ft (1830 mm). (2) The maximum individual dispenser fluid capacity shall be as follows: (a) 0.32 gal (1.2 L) for dispensers in rooms, corridors, and areas open to corridors (b) 0.53 gal (2.0 L) for dispensers in suites of rooms (3) Where aerosol containers are used, the maximum capacity of the aerosol dispenser shall be 18 oz. (0.51 kg) and shall be limited to Level 1 aerosols as defined in NFPA 30B,. (4) (3) Dispensers shall be separated from one another by horizontal spacing of not less than 48 in. (1220 mm). (5) (4) Not more than an aggregate 10 gal (37.8 L) of alcohol-based hand-rub solution shall be in use outside of a storage cabinet in a single smoke compartment. (6) (5) Storage of quantities greater than 5 gal (18.9 L) in a single smoke compartment shall meet the requirements of NFPA 30,. (7) (6) Dispensers shall not be installed in the following locations: (a) Above an ignition source for a horizontal distance of 1 in. (25 mm) to each side of the ignition source (b) To the side of an ignition source within a 1 in. (25 mm) horizontal distance from the ignition source (c) Beneath an ignition source within a 1 in. (25 mm) vertical distance from the ignition source (8) (7) Dispensers installed directly over carpeted floors shall be permitted only in sprinklered smoke compartments. (9) The alcohol-based hand-rub solution shall not exceed 95 percent alcohol content by volume. (10) Operation of the dispenser shall comply with the following criteria: (a) The dispenser shall not release its contents except when the dispenser is activated, either manually or automatically by touch-free activation. (b) Any activation of the dispenser shall only occur when an object is placed within 4 in. (100 mm) of the sensing device. (c) An object placed within the activation zone and left in place shall not cause more than one activation. (d) The dispenser shall not dispense more solution than the amount required for hand hygiene consistent with label instructions (e) The dispenser shall be designed, constructed and operated in a manner that ensures accidental or malicious activation of the dispensing device are minimized. (f) The dispenser shall be tested in accordance with the manufacturer s care and use instructions each time a new refill is installed. The action inserts a new subitem (3) to recognize and regulate the aerosol form of alcohol-based solution. The same text was added to the health care occupancies chapters in NFPA 101 for the 2009 edition, but the same change could not be made to NFPA 5000 at that time because the issue has not been raised during the ROP phase of the revision process. New criteria for the manual or "touch free" automatic activation of the dispenser are being added as the current language does not make clear that automatic activation is permitted. A maximum limit on the alcohol content of the hand-rub solution as the percentage of alcohol is proposed so that the AHJ does not limit the percentage to less than needed for infection control. The alcohol content has increased since the devices were first introduced. The maximum 95 percent alcohol by volume limitation recognizes that some, small percentage of the volume needs to be water to facilitate spreading the solution on hand surfaces. 13

15 Log #172 BLD-HEA Ignatius Kapalczynski, CT Office of State Fire Marshal DELETE section. Requirement is obsolete. The prior Committee Statement has been repeated without change. Explanation of this unusual contradiction, an example or scenario, or an actual application of this situation has not been offered. The need to justify self contradiction by an AHJ is not apparent. Delete or refer to NFPA 13 Technical Committee to re-evaluate. TC statement: The current provision is needed to prevent the Catch-22 situation where the AHJ prohibits the installation of sprinklers in a particular room and then rules that the building, because the room is unsprinklered, is not a fully sprinklered building. The requirement is not obsolete. If the AHJ prohibits sprinklers then the owner/operator needs the protection afforded by this provision so as not to permit the AHJ to turn around and classify an otherwise fully-sprinklered building as being non-sprinklered. The BLD-HEA committee stands by its decision from the 2009 edition cycle for NFPA 101 to retain the provision. 14

16 a Log #CP751 BLD-HEA Technical Committee on Health Care Occupancies, Revise as follows: Corridors used for exit access within the ambulatory health care occupancy shall comply with both of the following: (1) They shall be smoke partitions in accordance with Section (2) They shall have not less than a 1-hour fire resistance rating in accordance with Section 8.4 in other than smoke compartments protected throughout by an approved, electrically supervised automatic sprinkler system in accordance with Section In smoke compartments protected throughout by an approved, electrically supervised automatic sprinkler system in accordance with Section 55.3, corridor doors, other than fire protection-rated doors serving hazardous areas; exit enclosures; or vertical openings, shall meet all of the following: (1) They shall be self-latching. (2) They shall comply with through (3) They shall be self-closing or automatic-closing in accordance with where the non-rated door serves a sprinklered hazardous area. Every story of the ambulatory health care facility shall be divided into not less than two smoke compartments, unless one of the following conditions exists: (1) Facilities are less than 5000 ft2 (465 m2) and are protected by an approved automatic smoke detection system. (2) Facilities are less than 10,000 ft2(929 m2) and are protected throughout by an approved, electrically supervised automatic sprinkler system installed in accordance with Section (3) An area in an adjoining occupancy is permitted to serve as a smoke compartment for the ambulatory health care facility, and all of the following criteria also are met: (a) The separating wall and both compartments meet the requirements of (b) The ambulatory health care facility is less than 22,500 ft2 (2100 m2). (c) Access from the ambulatory health care facility to the other occupancy is unrestricted. Doors in smoke barriers shall comply with all of the following: (1) They shall be not less than 1¾ in. (44 mm) thick, solid-bonded wood core or the equivalent. (2) They shall be self-closing or automatic-closing in accordance with (3) They shall be provided with positive latching hardware on other than cross-corridor doors. (4) They shall be provided with a vision panel if the door is a cross-corridor door. (5) Vision panels in doors in smoke barriers, if provided, shall be of fire-rated glazing or wired glass in approved frames. The BLD-HEA committee was directed, by the Technical Correlating Committee, to review its occupancy chapter provisions that are of the list-type format and to revise, as needed, to clearly indicate whether the items in the lists apply to "all of", "one of", or "any of" the items. The revisions shown in the Recommendation field clarify intent. 15

17 b Log #CP753 BLD-HEA Technical Committee on Health Care Occupancies, Revise as follows:. The number of means of egress shall be in accordance with Section 7.4. Not less than two exits of the types described in that are remotely located from each other shall be provided for each floor or fire section of the building. Any room, or any suite of rooms, of more than 2500 ft 2 (232 m 2 ) shall have not less than two exit access doors remotely located from each other. Not less than two exits of the types described in shall be accessible from each smoke compartment. Egress shall be permitted through adjacent compartments but shall not require return through the compartment of fire origin. Correlation with changes being made to NFPA 101. The change is editorial and formatting in nature only. It makes no technical change Log #126 BLD-HEA Joshua W. Elvove, Aurora, CO Revise text to read as follows: Any room and any patient care suite of rooms of more than 2500 ft 2 (232 m 2 ) shall have not less than two exit access doors remotely located from each other. The need to specifically address the number of exit access doors in suites is because ambulatory health care occupancies commonly use this configuration (e.g., emergency departments, radiology suites, etc.), and without such language, there would be no guidance in this area. The business occupancy chapters make no mention of suites, so it must be assumed that the suite provisions are only meant to apply to patient care suites, not administrative suites. Hence, it s only fitting that the term patient care be added in front of the word suite. This also aligns the requirements of with the definition for patient care suites. Revise as follows: Any patient care room and any patient care suite of rooms of more than 2500 ft 2 (232 m 2 ) shall have not less than two exit access doors remotely located from each other. The committee action does what the submitter requested and also fixes an oversight by adding "patient care" before the word "room." 16

18 b Log #CP755 BLD-HEA Technical Committee on Health Care Occupancies, Revise as follows: Alcohol-based hand-rub dispensers shall be protected in accordance with Section 8.15 and Chapter 34, unless all of the following conditions are met: (1) Where dispensers are installed in a corridor, the corridor shall have a minimum width of 6 ft (1830 mm). (2) The maximum individual dispenser fluid capacity shall be as follows: (a) 0.32 gal (1.2 L) for dispensers in rooms, corridors, and areas open to corridors (b) 0.53 gal (2.0 L) for dispensers in suites of rooms (3) Where aerosol containers are used, the maximum capacity of the aerosol dispenser shall be 18 oz. (0.51 kg) and shall be limited to Level 1 aerosols as defined in NFPA 30B,. (4) (3) Dispensers shall be separated from one another by horizontal spacing of not less than 48 in. (1220 mm). (5) (4) Not more than an aggregate 10 gal (37.8 L) of alcohol-based hand-rub solution shall be in use outside of a storage cabinet in a single smoke compartment. (6) (5) Storage of quantities greater than 5 gal (18.9 L) in a single smoke compartment shall meet the requirements of NFPA 30,. (7) (6) Dispensers shall not be installed in the following locations: (a) Above an ignition source for a horizontal distance of 1 in. (25 mm) to each side of the ignition source (b) To the side of an ignition source within a 1 in. (25 mm) horizontal distance from the ignition source (c) Beneath an ignition source within a 1 in. (25 mm) vertical distance from the ignition source (8) (7) Dispensers installed directly over carpeted floors shall be permitted only in sprinklered smoke compartments. (9) The alcohol-based hand-rub solution shall not exceed 95 percent alcohol content by volume. (10) Operation of the dispenser shall comply with the following criteria: (a) The dispenser shall not release its contents except when the dispenser is activated, either manually or automatically by touch-free activation. (b) Any activation of the dispenser shall only occur when an object is placed within 4 in. (100 mm) of the sensing device. (c) An object placed within the activation zone and left in place shall not cause more than one activation. (d) The dispenser shall not dispense more solution than the amount required for hand hygiene consistent with label instructions (e) The dispenser shall be designed, constructed and operated in a manner that ensures accidental or malicious activation of the dispensing device are minimized. (f) The dispenser shall be tested in accordance with the manufacturer s care and use instructions each time a new refill is installed. The action inserts a new subitem (3) to recognize and regulate the aerosol form of alcohol-based solution. The same text was added to the health care occupancies chapters in NFPA 101 for the 2009 edition, but the same change could not be made to NFPA 5000 at that time because the issue has not been raised during the ROP phase of the revision process. New criteria for the manual or "touch free" automatic activation of the dispenser are being added as the current language does not make clear that automatic activation is permitted. A maximum limit on the alcohol content of the hand-rub solution as the percentage of alcohol is proposed so that the AHJ does not limit the percentage to less than needed for infection control. The alcohol content has increased since the devices were first introduced. The maximum 95 percent alcohol by volume limitation recognizes that some, small percentage of the volume needs to be water to facilitate spreading the solution on hand surfaces. 17

19 Log #125 BLD-HEA Joshua W. Elvove, Aurora, CO New text to read as follows: A Portions of buildings that are frequented by inpatients who are capable of self-preservation should not be classified as health care occupancies. The current definition of a health care occupancy is an occupancy used to provide medical or other treatment or care simultaneously to four or more patients on an inpatient basis, where such patients are mostly incapable of self-preservation due to age, physical or mental disability, or because of security measures not under the occupant s control. The provisions for health care occupancies (i.e., Chapter 19) should only be meant to apply to occupants who need staff assistance and additional safeguards to ensure their safety, because they aren t capable of providing this on their own. In many cases, inpatients are not necessarily incapable of self-preservation (e.g., post surgical ortho-rehab patients) yet currently, the health care occupancy provisions apply to any area where 4 or more such inpatients are treated (e.g., PT clinic). Though a complete revision of the existing definition is preferred, the proposed annex note is meant to alert users that just because an area in being used to treat 4 or more inpatients, it should not necessarily mean that the health care occupancy provisions of Chapter 19 need apply (i.e., the occupancy might be better classified as an ambulatory health care occupancy assuming it serves 4 or more patients). Note: in many instances, 4 or more inpatients can be found in the dining facility, yet we don t expect that area to comply with the health care occupancy chapter requirements. Hence, in areas where inpatients receive treatment, the nature of the treatment and the condition of the inpatient should dictate whether the health care occupancy chapter requirements should apply (i.e., base occupancy classification upon true risk). Note: similar language might also be appropriate in a new annex for The subject is already adequately covered by

New Fire Safety Rules Summary Evvie Munley, LeadingAge

New Fire Safety Rules Summary Evvie Munley, LeadingAge New Fire Safety Rules Summary Evvie Munley, LeadingAge Following is the link to the Centers for Medicare and Medicaid Services (CMS) Final Rule, Medicare and Medicaid Programs; Fire Safety Requirements

More information

Facility Demographic Report

Facility Demographic Report Facility Demographic Report Introduction and Overview (Revision 2017) Each healthcare facility is responsible for providing an environment in which to deliver healthcare services that are safe and hazard

More information

Adult Family Care Home Top Ten Health Deficiency Citations Statewide October 8, 2009 Year Date Range: January 1, 2008 through December 31, 2008

Adult Family Care Home Top Ten Health Deficiency Citations Statewide October 8, 2009 Year Date Range: January 1, 2008 through December 31, 2008 Rank Tag Count Description Adult Family Care Home 1 F0401 182 Personnel records must include verification of freedom from communicable disease for the AFCH provider, each relief person, each adult household

More information

E63-09/ (IFC [B] )

E63-09/ (IFC [B] ) Code Technology Committee 2010 Final Action Agenda The following are code changes and public comments to be considered at the 2010 Dallas Final Action Hearings that are related to the CTC Area of Study

More information

Department of Health Update

Department of Health Update PACAH Spring 2016 Department of Health Update Presented by: Susan Williamson, Director Division of Nursing Care Facilities Charlie Schlegel, Director Division of Safety Inspection Facility and Survey Data

More information

Center for Medicaid, CHIP, and Survey & Certification/Survey & Certification Group

Center for Medicaid, CHIP, and Survey & Certification/Survey & Certification Group DEPARTMENT OF HEALTH & HUMAN SERVICES Centers for Medicare & Medicaid Services 7500 Security Boulevard, Mail Stop 02-02-38 Baltimore, Maryland 21244-1850 Center for Medicaid, CHIP, and Survey & Certification/Survey

More information

Prepublication Requirements

Prepublication Requirements Issued Prepublication Requirements The Joint Commission has approved the following revisions for prepublication. While revised requirements are published in the semiannual updates to the print manuals

More information

Minnesota Health Care Engineers Association. Bob Dehler, P.E. Engineering Program Manager September 14, 2017

Minnesota Health Care Engineers Association. Bob Dehler, P.E. Engineering Program Manager September 14, 2017 Minnesota Health Care Engineers Association Bob Dehler, P.E. Engineering Program Manager September 14, 2017 All You Ever Wanted to Know About Healthcare Plan Review and Inspection Bob Dehler, P.E. Robert.Dehler@state.mn.us

More information

Life Safety Code Update for Hospitals and Nursing Homes May 3, 2012

Life Safety Code Update for Hospitals and Nursing Homes May 3, 2012 Life Safety Code Update for Hospitals and Nursing Homes May 3, 2012 James P. Loveland, P.E. Program Manager Minnesota Department of Health Engineering Services Section The Centers for Medicare and Medicaid

More information

SENIOR/ASSISTED LIVING FACILITY SPECIFIC QUESTIONNAIRE

SENIOR/ASSISTED LIVING FACILITY SPECIFIC QUESTIONNAIRE Corporate/Parent Name: SENIOR/ASSISTED LIVING FACILITY SPECIFIC QUESTIONNAIRE (please provide the following for each facility) Facility Specific Questionnaire Facility Description 1. Facility name: Location

More information

TOP 10 DEFICIENCIES, SECOND QUARTER FY 2015.xls

TOP 10 DEFICIENCIES, SECOND QUARTER FY 2015.xls STATE TOTAL NFPA 101 153 1 483.65 146 2 483.60(a),(b) 126 3 483.35(i) 119 4 0226 DEVELOP/IMPLMENT ABUSE/NEGLECT, ETC POLICIES The facility must develop and operationalize policies and procedures for screening

More information

How to Submit Waivers and Equivalencies

How to Submit Waivers and Equivalencies How to Submit Waivers and Equivalencies Tuesday, August 7, 2018 Presented by: Alise Howlett, Assoc. AIA, CFPE, CHFM Standards Advisor, EM/PE/LS HFAP A better healthcare survey experience 1 What We Will

More information

The Pre-Construction Risk Assessment

The Pre-Construction Risk Assessment The Pre-Construction Risk Assessment It Is The Right Thing to Do Gehring Health Facility Resources Our Premise The incomplete or ineffective implementation of the PCRA can increase the construction costs

More information

TESTING APPLICATION STANDARD (TAS) IMPACT TEST PROCEDURES

TESTING APPLICATION STANDARD (TAS) IMPACT TEST PROCEDURES TESTING APPLICATION STANDARD (TAS) 201-94 IMPACT TEST PROCEDURES 1. 2. Scope: 1.1 This protocol covers procedures for conducting the impact test of materials as required by Section 1626 of the Florida

More information

ANNEX 2 RESOLUTION MSC.216(82) (adopted on 8 December 2006)

ANNEX 2 RESOLUTION MSC.216(82) (adopted on 8 December 2006) RESOLUTION MSC.216(82) (adopted on 8 December 2006) ADOPTION OF AMENDMENTS TO THE INTERNATIONAL CONVENTION FOR THE SAFETY OF LIFE AT SEA, 1974, AS AMENDED THE MARITIME SAFETY COMMITTEE, RECALLING Article

More information

District of Columbia. Phone. Agency. Department of Health, Health Regulation and Licensing Administration (202)

District of Columbia. Phone. Agency. Department of Health, Health Regulation and Licensing Administration (202) District of Columbia Agency Department of Health, Health Regulation and Licensing Administration (202) 724-8800 Contact Sharon Mebane (202) 442-4751 E-mail sharon.mebane@dc.gov Phone Web Site http://doh.dc.gov/page/health-regulation-and-licensing-administration

More information

Medicare Conditions for Coverage 2009 Crosswalk

Medicare Conditions for Coverage 2009 Crosswalk Medicare Conditions for Coverage 2009 Crosswalk By Dawn Q. McLane RN, MSA, CASC, CNOR Note: Changes between CfC prior to 2009 and CfC 2009 are denoted in red. Medicare CfC prior to 2009 42 CFR Public Health

More information

MEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.

MEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot. National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: NEC Code-Making Panel 10 From: Kimberly Shea, Project Administrator

More information

Formal Interpretations Guidelines for Design and Construction of Hospitals and Outpatient Facilities, 2014 edition

Formal Interpretations Guidelines for Design and Construction of Hospitals and Outpatient Facilities, 2014 edition Formal Interpretations Guidelines for Design and Construction of Hospitals and Outpatient Facilities, 2014 edition Decisions published here were rendered after a multi-person panel of Health Guidelines

More information

TELECOMMUTING AGREEMENT

TELECOMMUTING AGREEMENT TELECOMMUTING AGREEMENT Telecommuting is a work option which, when properly implemented and administered, benefits both the staff member and Pepperdine. Telecommuting is not a right, but rather, a privilege

More information

DHS 83 Question & Answer Document (related to revisions made effective ) SUBCHAPTER I LICENSING: DHS DHS 83.03

DHS 83 Question & Answer Document (related to revisions made effective ) SUBCHAPTER I LICENSING: DHS DHS 83.03 DHS 83 Question & Answer Document (related to revisions made effective 4-1-09) SUBCHAPTER I LICENSING: DHS 83.01 DHS 83.03 1. Question: Section DHS 83.02(20) defines dietary supplement. How is it determined

More information

United States Liability Insurance Group Non Profit Social Service Organization

United States Liability Insurance Group Non Profit Social Service Organization United States Liability Insurance Group Non Profit Social Service Organization APPLICATION ALL QUESTIONS MUST BE ANSWERED AND APPLICATION MUST BE SIGNED BY APPLICANT. A. GENERAL INFORMATION Applicant -

More information

245D-HCBS Community Residential Setting (CRS) Licensing Checklist

245D-HCBS Community Residential Setting (CRS) Licensing Checklist 245D-HCBS Community Residential Setting (CRS) Licensing Checklist License Holder s Name: CRS License #: Program Address: Date of review: Type of review: Initial Renewal Other C = Compliance NC = Non-Compliance

More information

MINUTES HEALTHCARE INTERPRETATIONS TASK FORCE

MINUTES HEALTHCARE INTERPRETATIONS TASK FORCE MINUTES HEALTHCARE INTERPRETATIONS TASK FORCE Tuesday December 9, 2008 The Joint Commission - Room 335 One Renaissance Boulevard Oakbrook Terrace, IL 8:30 A.M. 5:00 P.M. 1. The meeting was called to order

More information

Standards. Successfully Preparing for Your Next AAAHC Accreditation Survey Annual Conference

Standards. Successfully Preparing for Your Next AAAHC Accreditation Survey Annual Conference Successfully Preparing for Your Next AAAHC Accreditation Survey 2012 Annual Conference Guest Speaker Ray Grundman, MSN, MPA, CASC AAAHC Senior Director External Relations AAAHC Surveyor AAAHC - Past President

More information

CMS Proposed Rule

CMS Proposed Rule CMS Proposed Rule 482.41 CMS: 2012 Life Safety Code Adoption 2014 American Society for Healthcare Engineering 155 N. Wacker Drive, Suite 400 Chicago, IL 60606 ashe.org ashe@aha.org 312-422-3800 Important

More information

First Revision No. 2-NFPA [ Sections 1.1, 1.2, 1.3 ]

First Revision No. 2-NFPA [ Sections 1.1, 1.2, 1.3 ] First Revision No. 2-NFPA 1091-2013 [ Sections 1.1, 1.2, 1.3 ] 1.1 Scope. This standard identifies the minimum job performance requirements (JPRs) necessary to perform temporary traffic control duties

More information

Preparing for Life Safety Code Surveys with the Joint Commission - Part 2. Florida Hospital Association. Wednesday, May 2, 2018 WELCOME!

Preparing for Life Safety Code Surveys with the Joint Commission - Part 2. Florida Hospital Association. Wednesday, May 2, 2018 WELCOME! Preparing for Life Safety Code Surveys with the Joint Commission - Part 2 Florida Hospital Association 1 WELCOME! Thanks for joining us! 2 Florida Hospital Association 1 Part 1 Review Understand how The

More information

89421 WATER SUPPLY CLEARANCE Any home where water for human consumption is from a private source shall meet the following requirements:

89421 WATER SUPPLY CLEARANCE Any home where water for human consumption is from a private source shall meet the following requirements: 89421 FOSTER FAMILY HOMES Regulations 89421 WATER SUPPLY CLEARANCE 89421 Any home where water for human consumption is from a private source shall meet the following requirements: (1) Prior to the home

More information

DEPARTMENT OF HUMAN SERVICES SENIORS AND PEOPLE WITH DISABILITIES DIVISION OREGON ADMINISTRATIVE RULES CHAPTER 411

DEPARTMENT OF HUMAN SERVICES SENIORS AND PEOPLE WITH DISABILITIES DIVISION OREGON ADMINISTRATIVE RULES CHAPTER 411 DEPARTMENT OF HUMAN SERVICES SENIORS AND PEOPLE WITH DISABILITIES DIVISION OREGON ADMINISTRATIVE RULES CHAPTER 411 DIVISION 57 INDORSEMENT OF ALZHEIMER'S CARE UNITS 411-057-0000 Statement of Purpose (1)

More information

The Joint Commission and Facility Design: A Partnership for Patient Safety and Quality Care

The Joint Commission and Facility Design: A Partnership for Patient Safety and Quality Care The Joint Commission and Facility Design: A Partnership for Patient Safety and Quality Care A Webinar Presentation for the AIA AAH 8 January 2013 1 Topic 1: Driving Safety through Good Design Presenter:

More information

SAMPLE: Environmental Rounds and Safety Assessment Tool

SAMPLE: Environmental Rounds and Safety Assessment Tool SAMPLE: Environmental Rounds and Safety Assessment Tool Area/Department Evaluated: Date: Security and Incident Management Y N N/A Comments 1. Are emergency telephone numbers posted by all stationary phones?

More information

Eleganza 3XC. Designed for ICU

Eleganza 3XC. Designed for ICU Eleganza 3XC Designed for ICU Benefits of Eleganza 3XC 2 LINET Eleganza 3XC Everything needed to save lives Prevention of pulmonary and cardiac complications Falls protection and pressure ulcer prevention

More information

RULE 203 FAMILY Adult Foster Care With a 245D-HCBS Program License Licensing Checklist

RULE 203 FAMILY Adult Foster Care With a 245D-HCBS Program License Licensing Checklist RULE 203 FAMILY Adult Foster Care With a 245D-HCBS Program License Licensing Checklist License Holder s Name: AFC License #: Program Address: Date of review: (indicate type) Initial Renewal Other C = Compliance

More information

Emergency Preparedness

Emergency Preparedness In the interest of maintaining a safe environment for all visitors at Stanford University, it is important for your program s staff and participants to know the following procedures in the unlikely event

More information

How To Navigate the. FGI Guidelines

How To Navigate the. FGI Guidelines How To Navigate the FGI Guidelines AARON JEFFERS Greenville, SC ajeffers@mcmillanpazdansmith.com SAMUEL WALKER Charlotte, NC sam.walker@mcmillanpazdansmith.com Agenda About the FGI How to use the guidelines

More information

Adopted Amendments: N.J.A.C. 14:7-1.4, 1.8, 1.9, 1.11, 1.12, 1.14, 1.20, 1.24, 1.25, and 2.3

Adopted Amendments: N.J.A.C. 14:7-1.4, 1.8, 1.9, 1.11, 1.12, 1.14, 1.20, 1.24, 1.25, and 2.3 NEW JERSEY BOARD OF PUBLIC UTILITIES Adopted Amendments to the Natural Gas Pipeline Rules N.J.A.C. 14:7-1.4, 1.8, 1.9, 1.11, 1.12, 1.14, 1.20, 1.24, 1.25, and 2.3 Docket No. GX08121086 PUBLIC UTILITIES...1

More information

ADMINISTRATIVE INSTRUCTION

ADMINISTRATIVE INSTRUCTION Director Administration and Management Deputy Chief Management Officer of the Department of Defense ADMINISTRATIVE INSTRUCTION NUMBER 103 October 20, 2008 Incorporating Change 1, July 17, 2017 DFD FSD,

More information

Texas Commission on Environmental Quality

Texas Commission on Environmental Quality Texas Commission on Environmental Quality Instructions: Applying for a Use Determination for Pollution Control Property through STEERS There are now two ways to apply for a Use Determination for Pollution

More information

Hospital Construction, Renovation, and Demolition

Hospital Construction, Renovation, and Demolition 01.38 - Hospital Construction, Renovation, and Demolition Purpose Infection Control Risk Assessment (ICRA) To provide infection control guidelines for hospital construction, renovation, and demolition.

More information

STATE OF MICHIGAN DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS LANSING

STATE OF MICHIGAN DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS LANSING RICK SNYDER GOVERNOR June 7, 2018 STATE OF MICHIGAN DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS LANSING SHELLY EDGERTON DIRECTOR Kasmire Pham A Plus Quality Home Care 21885 South Tuller Court Southfield,

More information

Emergency Management. 1 of 8 Updated: June 20, 2014 Hospice with Residential Facilities

Emergency Management. 1 of 8 Updated: June 20, 2014 Hospice with Residential Facilities CEMP Criteria for Hospice Lee County Emergency Management The following criteria are to be used when developing Comprehensive Emergency Management Plans (CEMP) for all hospices. The criteria also serve

More information

Table of Contents. FREQUENTLY ASKED QUESTIONS Iowa ServiceMatters/PathTracker Webinars 1/25/2016 2/2/2016. PASRR/Level I Questions...

Table of Contents. FREQUENTLY ASKED QUESTIONS Iowa ServiceMatters/PathTracker Webinars 1/25/2016 2/2/2016. PASRR/Level I Questions... Below you will find the frequently asked questions for the ServiceMatters and PathTracker Webinars conducted 1/25/2016 2/2/2016. Answers to these questions were based on knowledge and policy as of 3/1/2016.

More information

SUBCHAPTER 31. MANDATORY PHYSICAL ENVIRONMENT

SUBCHAPTER 31. MANDATORY PHYSICAL ENVIRONMENT SUBCHAPTER 31. MANDATORY PHYSICAL ENVIRONMENT 8:39-31.1 Mandatory construction standards (a) No construction, renovation or addition shall be undertaken without first obtaining approval from the Department,

More information

ALABAMA BOARD OF NURSING ADMINISTRATIVE CODE CHAPTER 610-X-5 ADVANCED PRACTICE NURSING COLLABORATIVE PRACTICE TABLE OF CONTENTS

ALABAMA BOARD OF NURSING ADMINISTRATIVE CODE CHAPTER 610-X-5 ADVANCED PRACTICE NURSING COLLABORATIVE PRACTICE TABLE OF CONTENTS Nursing Chapter 610-X-5 ALABAMA BOARD OF NURSING ADMINISTRATIVE CODE CHAPTER 610-X-5 ADVANCED PRACTICE NURSING COLLABORATIVE PRACTICE TABLE OF CONTENTS 610-X-5-.01 610-X-5-.02 610-X-5-.03 610-X-5-.04 610-X-5-.05

More information

TITLE 17. PUBLIC HEALTH DIVISION 2. HEALTH AND WELFARE AGENCY CHAPTER 3. COMMUNITY SERVICES SUBCHAPTER 24. ENHANCED BEHAVIORAL SUPPORTS HOMES

TITLE 17. PUBLIC HEALTH DIVISION 2. HEALTH AND WELFARE AGENCY CHAPTER 3. COMMUNITY SERVICES SUBCHAPTER 24. ENHANCED BEHAVIORAL SUPPORTS HOMES TITLE 17. PUBLIC HEALTH DIVISION 2. HEALTH AND WELFARE AGENCY CHAPTER 3. COMMUNITY SERVICES SUBCHAPTER 24. ENHANCED BEHAVIORAL SUPPORTS HOMES 59050. Definitions. The following definitions shall apply to

More information

SPECIFICATIONS FOR TENDER # SUPPLY OF HOSPITAL CRITICAL CARE BED FOR WESTERN HEALTH

SPECIFICATIONS FOR TENDER # SUPPLY OF HOSPITAL CRITICAL CARE BED FOR WESTERN HEALTH SPECIFICATIONS FOR TENDER #0171-1203 SUPPLY OF HOSPITAL CRITICAL CARE BED FOR WESTERN HEALTH CLOSING DATE: 3 FEBRUARY 2012 Invitation to Tender for Hospital Critical Care Beds 1.0 General Provisions 1.1

More information

N.J.A.C. 5: New Jersey Register, Vol. 49 No. 12, June 19, 2017

N.J.A.C. 5: New Jersey Register, Vol. 49 No. 12, June 19, 2017 -1.1 SUBCHAPTER 1. GENERAL PROVISIONS 5:12-1.1 Title and citation This regulation shall be known and may be cited as N.J.A.C. 5:12, Ski Lifts. Page 2 of 30 N.J.A.C. 5:12-1.2 SUBCHAPTER 1. GENERAL PROVISIONS

More information

Standard EC Elements of Performance for EC The hospital manages fire risks.

Standard EC Elements of Performance for EC The hospital manages fire risks. Standard EC.02.03.01 The hospital manages fire risks. Elements of Performance for EC.02.03.01 1. The hospital minimizes the potential for harm from fire, smoke, and other products of combustion. 2. If

More information

S.I. No. XX of 201X SAFETY, HEALTH AND WELFARE AT WORK (ONSHORE AND OFFSHORE DRILLING) REGULATIONS, 2014 ARRANGEMENT OF REGULATIONS.

S.I. No. XX of 201X SAFETY, HEALTH AND WELFARE AT WORK (ONSHORE AND OFFSHORE DRILLING) REGULATIONS, 2014 ARRANGEMENT OF REGULATIONS. S.I. No. XX of 201X SAFETY, HEALTH AND WELFARE AT WORK (ONSHORE AND OFFSHORE DRILLING) REGULATIONS, 2014 1. Citation and commencement 2. Interpretation 3. Application General Safety, Health and Welfare

More information

EXISTING CONDITIONS

EXISTING CONDITIONS 02 00 00 EXISTING CONDITIONS 02 01 00 Maintenance of Existing Conditions 02 01 50 Maintenance of Site Remediation 02 01 65 Maintenance of Underground Storage Tank Removal 02 01 80 Maintenance of Facility

More information

TELECOMMUTING WORK AGREEMENT

TELECOMMUTING WORK AGREEMENT TELECOMMUTING WORK AGREEMENT The following Telecommuting Agreement ( Agreement ) is made and entered into as of the day of, 20 (the Effective ) by and between William & Mary in Virginia (the University

More information

LAKEWOOD FIRE DEPARTMENT STANDARD OPERATING GUIDELINES

LAKEWOOD FIRE DEPARTMENT STANDARD OPERATING GUIDELINES LAKEWOOD FIRE DEPARTMENT STANDARD OPERATING GUIDELINES SOG NUMBER: 301.02 EMERGENCY OPERATIONS DATE IMPLEMENTED: MAY 8, 2017 DATE REVISED: TITLE: FIREGROUND OPERATIONS PURPOSE: This provision was promulgated

More information

Date: September 2, Assisted Living Facilities (ALFs) To:

Date: September 2, Assisted Living Facilities (ALFs) To: COMMISSIONER Jon Weizenbaum Date: To: Subject: September 2, 2016 Assisted Living Facilities (ALFs) Provider Letter No. 16-34 Initial License for a Type A or Type B ALF for an Applicant in Good Standing

More information

Using Body Mechanics

Using Body Mechanics Promotion of Safety Using Body Mechanics Muscles work best when used correctly Correct use of muscles makes lifting, pulling, and pushing easier Prevents unnecessary fatigue and strain and saves energy

More information

Oklahoma Department of Environmental Quality

Oklahoma Department of Environmental Quality Oklahoma Department of Environmental Quality EPA ID# Hazardous Waste LARGE QUANTITY GENERATOR INSPECTION REPORT Name of Facility Owner/Operator Phone Facility Mailing Address City Zip Code County Oklahoma

More information

MEDICAL UNIVERSITY OF SOUTH CAROLINA DEPARTMENT OF PUBLIC SAFETY. EFFECTIVE DATE: 1 January 1999 PAGE 1 OF 9

MEDICAL UNIVERSITY OF SOUTH CAROLINA DEPARTMENT OF PUBLIC SAFETY. EFFECTIVE DATE: 1 January 1999 PAGE 1 OF 9 MEDICAL UNIVERSITY OF SOUTH CAROLINA DEPARTMENT OF PUBLIC SAFETY POLICY AND PROCEDURE #49 SUBJECT: Building Checks and Searches EFFECTIVE DATE: 1 January 1999 PAGE 1 OF 9 REVIEW DATE: 30 November 2017

More information

Sarasota Memorial Hospital Laurel Road Update

Sarasota Memorial Hospital Laurel Road Update Public Workshop June 19, 2018 s Sarasota Memorial Hospital Laurel Road Update David Verinder, President & CEO, Sarasota Memorial Health Care System Steve Jackson, Principal, Flad Architects 1 Public Workshop

More information

Health and Safety Policy

Health and Safety Policy Health and Safety Policy Statement of intent: It is the policy of Step by Step School to comply with the terms of the Health and Safety at Work Act 1974 and subsequent legislation to provide and maintain

More information

ALABAMA BOARD OF MEDICAL EXAMINERS ADMINISTRATIVE CODE CHAPTER 540-X-8 ADVANCED PRACTICE NURSES: COLLABORATIVE PRACTICE TABLE OF CONTENTS

ALABAMA BOARD OF MEDICAL EXAMINERS ADMINISTRATIVE CODE CHAPTER 540-X-8 ADVANCED PRACTICE NURSES: COLLABORATIVE PRACTICE TABLE OF CONTENTS Medical Examiners Chapter 540-X-8 ALABAMA BOARD OF MEDICAL EXAMINERS ADMINISTRATIVE CODE CHAPTER 540-X-8 ADVANCED PRACTICE NURSES: COLLABORATIVE PRACTICE TABLE OF CONTENTS 540-X-8-.01 540-X-8-.02 540-X-8-.03

More information

St Helens Council Home Improvement Agency

St Helens Council Home Improvement Agency St Helens Council Home Improvement Agency Home From Hospital The Impact of HIA Interventions 21 June 2016 Lee Norman Manager Private Sector Housing Services Background to St Helens St Helens in Merseyside

More information

Audio Title: Revised and Clarified Place of Service (POS) Coding Instructions Audio Date: 6/3/2015 Run Time: 16:03 Minutes ICN:

Audio Title: Revised and Clarified Place of Service (POS) Coding Instructions Audio Date: 6/3/2015 Run Time: 16:03 Minutes ICN: Audio Title: Revised and Clarified Place of Service (POS) Coding Instructions Audio Date: 6/3/2015 Run Time: 16:03 Minutes ICN: 909207 Welcome to Medicare Learning Network Podcasts at the Centers for Medicare

More information

ELECTRICAL INSPECTION ACT CANADIAN ELECTRICAL CODE REGULATIONS

ELECTRICAL INSPECTION ACT CANADIAN ELECTRICAL CODE REGULATIONS c t ELECTRICAL INSPECTION ACT CANADIAN ELECTRICAL CODE REGULATIONS PLEASE NOTE This document, prepared by the Legislative Counsel Office, is an office consolidation of this regulation, current to June

More information

1403 Second Draft Ballot Results SR 10, Section No , See SR 10 Eligible to Vote: 31 Not Returned : 3 Gagliano, Herndon, Jr.

1403 Second Draft Ballot Results SR 10, Section No , See SR 10 Eligible to Vote: 31 Not Returned : 3 Gagliano, Herndon, Jr. 1403 Second Draft Ballot Results SR 10, Section No. 1.3.3, See SR 10 Gagliano, Herndon, Jr., O'Donnell Affirmative with Comment 0 Negative 1 Taken out according to language in the comments. SR 15, New

More information

NICU Lighting Redesign

NICU Lighting Redesign NICU Lighting Redesign Space Description The Neonatal Intensive Care Unit is located on the third floor of the new addition. Instead of looking at this area as a whole, it was broken down into two separate

More information

Contents. Preface Acknowledgments About this Document Major Additions and Revisions. List of Acronyms. Part 1 General 1

Contents. Preface Acknowledgments About this Document Major Additions and Revisions. List of Acronyms. Part 1 General 1 Contents Preface Acknowledgments About this Document Major Additions and Revisions Glossary List of Acronyms xv xvii xxiii xxix xxxiii xxxix Part 1 General 1 1.1 Introduction 1 1.1-1 General 1 1.1-1.1

More information

Patient Safety (PS) 1) A collaborative process is used to develop policies and/or procedures that address the accuracy of patient identification.

Patient Safety (PS) 1) A collaborative process is used to develop policies and/or procedures that address the accuracy of patient identification. Patient Safety (PS) Standard PS.1 [Patient identification] The organization has established procedures for accurately identifying patients. Intent of PS.1 Wrong-patient errors occur in virtually all aspects

More information

No. 22 in In accordance to articles 152 & 108 / second of Labor Law no. (71) of 1987 we decided to issue the following instructions:

No. 22 in In accordance to articles 152 & 108 / second of Labor Law no. (71) of 1987 we decided to issue the following instructions: No. 22 in 1987 Occupational Health and Safety Instructions In accordance to articles 152 & 108 / second of Labor Law no. (71) of 1987 we decided to issue the following instructions: Article one: these

More information

(b) Artificial Tanning Device shall mean any equipment that as defined in Section (1), C.R.S. 1989, as amended.

(b) Artificial Tanning Device shall mean any equipment that as defined in Section (1), C.R.S. 1989, as amended. DEPARTMENT OF PUBLIC HEALTH AND ENVIRONMENT Division of Environmental Health and Sustainability ARTIFICIAL TANNING DEVICE REGULATIONS 6 CCR 1010-20 [Editor s Notes follow the text of the rules at the end

More information

Planning for Improved Access and Orientation Anjali Joseph Jain EDRA 35

Planning for Improved Access and Orientation Anjali Joseph Jain EDRA 35 Hospital planning strategies for improving patient access and orientation within the hospital Anjali Joseph, College of Architecture, Georgia Institute of Technology Most hospitals have been designed through

More information

Public School Security Workshops

Public School Security Workshops Public School Security Workshops Artesia: April 13, 1:00-4:00 PM Santa Rosa: April 16, 1:00-4:00 PM Albuquerque: April 17, 9:00 AM-12:00 PM Deming: April 19, 1:00 PM-4:00 PM Gallup: April 24, 9:00 AM-12:00

More information

Simply Intuitive. The Hill-Rom Advanta 2 Bed

Simply Intuitive. The Hill-Rom Advanta 2 Bed Simply Intuitive. The Hill-Rom Advanta 2 Bed The Care Grip patient egress assist handle is designed to facilitate safer bed entry and exit by providing ergonomically correct leverage for patients. WE LISTENED

More information

Georgia. Phone. Agency Georgia Department of Community Health, Healthcare Facility Regulation Division (404)

Georgia. Phone. Agency Georgia Department of Community Health, Healthcare Facility Regulation Division (404) Georgia Agency Georgia Department of Community Health, Healthcare Facility Regulation Division (404) 657-5850 Contact Elaine Wright (404) 657-5856 E-mail ehwright@dch.ga.gov Phone Web Site http://dch.georgia.gov/healthcare-facility-regulation-0

More information

FIRE OFFICER I NFPA 1021, Chapter 4, 2014 Edition

FIRE OFFICER I NFPA 1021, Chapter 4, 2014 Edition Official Skill Sheets for Practical Skills Ontario, Canada FIRE OFFICER I NFPA 1021, Chapter 4, 2014 Edition National Fire Protection Association Standard for Fire Officer Professional Qualifications Enquiries

More information

19 Mo. Code of State Regulations CSR Definitions

19 Mo. Code of State Regulations CSR Definitions 19 Mo. Code of State Regulations 30-61.010 19 CSR 30-61.010 Definitions PURPOSE: This rule defines the terms used in the licensing rules for family day care homes. (1) Adult is any individual eighteen

More information

Incident Command System Awareness Participant Guide May 2016

Incident Command System Awareness Participant Guide May 2016 Incident Command System Awareness Participant Guide May 2016 Copyright 2016 Midwest Consortium for Hazardous Waste Worker Training Acknowledgments The Midwest Consortium developed this course for Hazardous

More information

C. Physician s orders for medication, treatment, care and diet shall be reviewed and reordered no less frequently than every two (2) months.

C. Physician s orders for medication, treatment, care and diet shall be reviewed and reordered no less frequently than every two (2) months. SECTION 1300 - MEDICATION MANAGEMENT 1301. General A. Medications, including controlled substances, medical supplies, and those items necessary for the rendering of first aid shall be properly managed

More information

Facility and Equipment Assessments and Hands-on Equipment Training

Facility and Equipment Assessments and Hands-on Equipment Training SPH Training Series Session 2 Facility and Equipment Assessments and Hands-on Equipment Training Western New York Council on Occupational Safety & Health (WNYCOSH) This material was produced under grant

More information

RALF Behavior Management Rules IDAPA

RALF Behavior Management Rules IDAPA RALF Behavior Management Rules IDAPA 16.03.22 DEFINITIONS: 010.10. Assessment. The conclusion reached using uniform criteria which identifies resident strengths, weaknesses, risks and needs, to include

More information

July 1, 2017 EMERGENCY PROCEDURES FOR DEPARTMENT OF ALLIED HEALTH SCIENCES IN BONDURANT HALL

July 1, 2017 EMERGENCY PROCEDURES FOR DEPARTMENT OF ALLIED HEALTH SCIENCES IN BONDURANT HALL EMERGENCY PROCEDURES FOR DEPARTMENT OF ALLIED HEALTH SCIENCES IN BONDURANT HALL These procedures set forth the steps to be followed in the event of an emergency. It is important that all employees thoroughly

More information

SECTION HOSPITALS: OTHER HEALTH FACILITIES

SECTION HOSPITALS: OTHER HEALTH FACILITIES SECTION.1400 - HOSPITALS: OTHER HEALTH FACILITIES 21 NCAC 46.1401 REGISTRATION AND PERMITS (a) Registration Required. All places providing services which embrace the practice of pharmacy shall register

More information

1 What is an AAAHC/Medicare Deemed Status survey? 2 What are the Medicare Conditions for Coverage (CfC)?

1 What is an AAAHC/Medicare Deemed Status survey? 2 What are the Medicare Conditions for Coverage (CfC)? FREQUENTLY ASKED QUESTIONS ABOUT MEDICARE DEEMED STATUS SURVEYS 1 What is an AAAHC/Medicare Deemed Status survey? The Centers for Medicare and Medicaid Services (CMS) accepts AAAHC s recommendation for

More information

MMO

MMO MMO 3500 www.mmomedical.fr MMO 3500 The MMO 3500 bedframe is equipped with 3 segment side-rails. It has been spefically developed to offer a high level of autonomy to the patients, whilst guaranteeing

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 24 FED - I0000 - INITIAL COMMENTS Title INITIAL COMMENTS CFR Type Memo Tag FED - I0007 - COMPLIANCE W/ FED, STATE, & LOCAL LAWS Title COMPLIANCE W/ FED, STATE, & LOCAL LAWS CFR 485.707 The organization

More information

Department of Health and Mental Hygiene Springfield Hospital Center

Department of Health and Mental Hygiene Springfield Hospital Center Audit Report Department of Health and Mental Hygiene Springfield Hospital Center April 2009 OFFICE OF LEGISLATIVE AUDITS DEPARTMENT OF LEGISLATIVE SERVICES MARYLAND GENERAL ASSEMBLY This report and any

More information

QUESTIONS. Print Student s/faculty Name: Date of Test Completion: Site of Experience: School/University: Semester:

QUESTIONS. Print Student s/faculty Name: Date of Test Completion: Site of Experience: School/University: Semester: 2017 - QUESTIONS Print Student s/faculty Name: Date of Test Completion: Site of Experience: School/University: Semester: Instructions: Read each question, write an answer on space provided, and return

More information

ND CAH Quality Pre-Conference

ND CAH Quality Pre-Conference ND CAH Quality Pre-Conference Bridget Weidner Health Facilities Program Manager June 18, 2014 Objectives Upon completion, the active participant will: Review the top deficiencies in Critical Access Hospitals

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 24 FED - I0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag FED - I0007 - COMPLIANCE W/ FED, STATE, & LOCAL LAWS Title COMPLIANCE W/ FED, STATE, & LOCAL LAWS Type Condition 485.707

More information

Wisconsin. Phone. Agency Department of Health Services, Division of Quality Assurance, Bureau of Assisted Living (608)

Wisconsin. Phone. Agency Department of Health Services, Division of Quality Assurance, Bureau of Assisted Living (608) Wisconsin Agency Department of Health Services, Division of Quality Assurance, Bureau of Assisted Living (608) 266-8598 Contact Alfred C. Johnson (608) 266-8598 E-mail Alfred.Johnson@dhs.wisconsin.gov

More information

130 FERC 61,211 UNITED STATES OF AMERICA FEDERAL ENERGY REGULATORY COMMISSION

130 FERC 61,211 UNITED STATES OF AMERICA FEDERAL ENERGY REGULATORY COMMISSION 130 FERC 61,211 UNITED STATES OF AMERICA FEDERAL ENERGY REGULATORY COMMISSION Before Commissioners: Jon Wellinghoff, Chairman; Marc Spitzer, Philip D. Moeller, and John R. Norris. Mandatory Reliability

More information

BED RAIL SAFETY 9/15/2015. A Clinical Process Guideline. Background. Federal Nursing Home Reform Act

BED RAIL SAFETY 9/15/2015. A Clinical Process Guideline. Background. Federal Nursing Home Reform Act BED RAIL SAFETY A Clinical Process Guideline Laura Funsch, RN, BSN, MS Director of Regulatory Strategy, LeadingAge Michigan Background Safety hazards related to bed rail use have been realized since 1990.

More information

SECTION EARTHQUAKE

SECTION EARTHQUAKE SECTION 11.14 EARTHQUAKE PROCEDURES TO BE FOLLOWED IN THE EVENT THAT A SIGNIFICANT EARTHQUAKE AFFECTS LOMA LINDA UNIVERSITY MEDICAL CENTER PREPARATION Education and Training: 1. The Safety Officers oversee

More information

RELEVANT STATE STANDARDS OF CARE AND SERVICES AND PROCESSES TO ENSURE STANDARDS ARE MET 1

RELEVANT STATE STANDARDS OF CARE AND SERVICES AND PROCESSES TO ENSURE STANDARDS ARE MET 1 Appendix D RELEVANT STATE STANDARDS OF CARE AND SERVICES AND PROCESSES TO ENSURE STANDARDS ARE MET 1 I. STATE STANDARDS OF CARE AND SERVICES Excerpts From RSA 171-A 171-A:1 Purpose and Policy. The purpose

More information

Hill-Rom Advanta 2 Bed Tips Simply Intuitive FOR COMPLETE INSTRUCTIONS ON HOW TO OPERATE THE ADVANTA 2 BED, SEE USER S MANUAL.

Hill-Rom Advanta 2 Bed Tips Simply Intuitive FOR COMPLETE INSTRUCTIONS ON HOW TO OPERATE THE ADVANTA 2 BED, SEE USER S MANUAL. Hill-Rom Advanta 2 Bed Tips Simply Intuitive FOR COMPLETE INSTRUCTIONS ON HOW TO OPERATE THE ADVANTA 2 BED, SEE USER S MANUAL. 1 Three-Mode Bed Exit System (Patient Position Monitor) The Bed Exit Alarm

More information

F Physical Environment The facility must be designed, constructed, equipped, and maintained to protect the health and safety of residents,

F Physical Environment The facility must be designed, constructed, equipped, and maintained to protect the health and safety of residents, F454 483.70 Physical Environment The facility must be designed, constructed, equipped, and maintained to protect the health and safety of residents, personnel and the public. 483.70(a) Life Safety From

More information

Performance Standard Procedures Person(s) Responsible (a)

Performance Standard Procedures Person(s) Responsible (a) 1310.10(a) 1) to and from center-based programs AA, ED is provided through contracted services with local providers. 2) Bussing is made available to all children enrolled in center-based classrooms, within

More information

Standard operating procedures for the conduct of outreach training and supportive supervision

Standard operating procedures for the conduct of outreach training and supportive supervision The MalariaCare Toolkit Tools for maintaining high-quality malaria case management services Standard operating procedures for the conduct of outreach training and supportive supervision Download all the

More information

CHEMICAL HYGIENE PLAN

CHEMICAL HYGIENE PLAN SAMPLE WRITTEN CHEMICAL HYGIENE PLAN For Compliance With 29 CFR 1910.1450 Wyoming General Rules and Regulations Wyoming Department of Workforce Services OSHA Division Consultation Program ACKNOWLEDGEMENTS

More information

San Francisco General Hospital ENVIRONMENT OF CARE (EOC)/SAFETY MANAGEMENT 2006 Annual Report

San Francisco General Hospital ENVIRONMENT OF CARE (EOC)/SAFETY MANAGEMENT 2006 Annual Report San Francisco General Hospital ENVIRONMENT OF CARE (EOC)/SAFETY MANAGEMENT 2006 Annual Report The intent of SFGH s EOC/Safety Program is to provide for a safe and effective environment of care for patients,

More information

Incident Planning Guide: Infectious Disease

Incident Planning Guide: Infectious Disease Incident Planning Guide: Infectious Disease Definition This Incident Planning Guide is intended to address issues associated with infectious disease outbreaks. Infectious disease incidents can come from

More information