Generator Interconnection Facilities Study Report Franklin County, NC 50.0 MW Solar Farm Queue #384

Similar documents
Generator Interconnection Impact Study Report Bladen County, NC 75.0 MW Solar Farm Queue #377

Generator Interconnection Impact Study Report Wayne County, NC 20.0 MW Solar Farm Queue #364

Generator Interconnection System Impact Study Report Carteret County, NC MW Queue #297 Original Submittal Revision 1

ATTACHMENT B. 1. Intent to Bid/Bidder Contact Information Form. 2. Executive Summary. 3. Proposal Characteristics and Term Sheet

Standard Development Timeline

Bio Energy #1 Distribution Generator Interconnections Less than 35 kv

XXXXX Kwalsa Phase II Project. Interconnection Facilities Study and Project Plan

Small and Large Generator Interconnection Procedures

OC Approved 2/17/05 SB/DS Stability Limits for the addition of 3.26% Series Reactor

Future Development Plan:

NPCC Tasks Related to NERC Blackout Recommendations Timeline

A. General provisions and other electrical systems are specified in other Sections of Division 26.

The State of Interconnection in NYS:

Addendum to ESAH Version 3 Supply Application

107 FERC 61,053 UNITED STATES OF AMERICA FEDERAL ENERGY REGULATORY COMMISSION

UNITED STATES OF AMERICA BEFORE THE FEDERAL ENERGY REGULATORY COMMISSION ) ) )

j. Billing procedure k. Periodical Inspections Page 1

NPCC Tasks Related to NERC Blackout Recommendations Timeline

Southern California Edison Original Cal. PUC Sheet No E Rosemead, California (U 338-E) Cancelling Cal. PUC Sheet No.

STATE OF NORTH CAROLINA UTILITIES COMMISSION RALEIGH DOCKET NO. E-2, SUB 1089 BEFORE THE NORTH CAROLINA UTILITIES COMMISSION

Transmission Planning Attachment K Public Input Meeting

RG 102 Accreditation for the Inspection of Non-public High Voltage Electrical Systems

PART 1 - Rules and Regulations for the Renewable Energy Development Fund Programs

TRIP OF YALLOURN POWER STATION NO KV BUSBAR ON 6 DECEMBER 2015

Energy Efficiency Alberta Residential and Commercial Solar Program Guidebook

AUSTIN ENERGY REQUEST FOR PROPOSALS (RFP) FOR THE PURCHASE OF RENEWABLE CAPACITY & ENERGY FROM RENEWABLE ENERGY RESOURCES

Standard NUC Nuclear Plant Interface Coordination

To ensure system protection is coordinated among operating entities.

ADVERTISEMENT OF PUBLIC NOTICE

If any queries arise ESB Networks DAC can be contacted at or

Pilot Program Framework Proposal

Comprehensive Interconnection Process Improvements

B. All of the documents in this RFP form the Basis-of-Design for this project.

Washington Headquarters Services Military Construction, Defense-Wide FY 2010 Budget Estimates ($ in thousands)

TECHNICAL DAYS, APRIL 2017 ABB Plant Fingerprint Assessment Optimizing Operations. Fernando Tobar, Country Service Manager

WECC Standard VAR-STD-2a-1 Automatic Voltage Regulators

The Narragansett Electric Company d/b/a National Grid

CIP Cyber Security Incident Reporting and Response Planning

Luis Fondacci. James Manning. Administrative. The November 14, 2016 OSC Meeting Minutes and Highlights were reviewed and approved with one edit.

Community Update Brochure

Request for Proposals and Specifications for a Distributed Generation Solar Project entitled The Freeman Coliseum Solar Project

2017 All Source Request for Proposals for Electric Power Supply and Load Management Resources. Pre-Bid Meeting

Implementation Plan Set Two of Phase III & IV Reliability Standards

Energy Efficiency Alberta Residential and Commercial Solar Program Terms and Conditions

July 1, 2006 Revision 2

UNIFIED FACILITIES GUIDE SPECIFICATIONS

Invitation to Submit Expression of Interest and Proposal

Standard FAC Facility Ratings. A. Introduction

APPENDIX 2: Electrical Design

Annual Performance Indicator (PI)

Energy. Request For Proposals for Renewable Power Supply Resources

The University of Texas at San Antonio

PER-005 System Personnel Training

Request for Proposals and Specifications for a Community Solar Project

PacifiCorp 2017S SOLAR Request for Proposals. Bidder s Conference Portland November 21, 2017

UCF SOLAR FARM-UCF 584 Solar Developer Project Fact Sheet

DEPARTMENT OF FACILITIES MANAGEMENT MAINTENANCE AND SERVICES INVITATION TO TENDER

TRANSMISSION TRANSMISSION SYSTEM OPERATIONS DIVISION

May 6, 2002 Revision 2

CITY OF COFFEYVILLE, KANSAS REQUEST FOR PROPOSALS FOR ELECTRICAL ENGINEERING, SUBSTATION MAINTENANCE, TESTING & SUPPORT SERVICES

Training and Evaluation Outline Report

WIND AND SOLAR SPP SOLICITATION 2015 REQUEST FOR QUALIFICATION (RFQ) COMMERCIAL OPERATION OF WIND AND SOLAR SMALL POWER PROJECTS OCTOBER 2015 FOR

WarmWise Business Custom Rebates Program Manual

NATIONAL NUCLEAR REGULATOR

Request for Qualifications. for. Electrical Substation Transformer Replacement. Stillwater Utilities Authority (SUA) City of Stillwater, Oklahoma

Electric Reliability Organization Event Analysis Process Phase 2 Field Test Draft May 2,

HT1611C Timer with Dialer Interface

PROMOTING REGIONAL ELECTRICITY TRADE IN CENTRAL ASIA. Paul Vallely Program Leader Central Asia Regional Office 6 September 2017

Greater Cambridge Partnership Executive Board. Chris Tunstall Interim Transport Director. Western Orbital

SunZia Southwest Transmission Project. September. Project Update for the Board of Socorro County Commissioners February 28, 2017.

Solar Energy Corporation of India Limited New Delhi

MLR Institute of Technology

CENTRAL MUNICIPAL POWER AGENCY/SERVICES

Buck & Boost Transformer Installation Instructions

AMSP Guidebook. February 2017

REQUEST FOR PROPOSALS

Siemens Power Academy Lagos Course Schedule

Mulilo Renewable Energy Solar PV Prieska (PTY) LTD

4.2.2 Transmission Owners Transmission Planners Transmission Service Providers Balancing Authorities.

Executive Council approves CLP Power s Five-Year Development Plan New Tariff and Monthly Fuel Cost Adjustment Come into Effect on 1 October

ELECTRONICS TECHNICIAN I ELECTRONICS TECHNICIAN II

Enduring Connection Policy Stage 1 (ECP-1)

Papua New Guinea: Implementation of the Electricity Industry Policy

The Narragansett Electric Company d/b/a National Grid

TOWN OF NEW TECUMSETH PROTOCOL FIT APPLICATIONS FOR RENEWABLE ENERGY

MRA4 Modbus HighPROTEC. Data point list. Manual DOK-TD-MRA4MDE

Feed-in Tariff: Guidance for renewable installations (Version 5)

P A N E L B O A R D S C H E D U L E

VREDENDAL SOLAR POWER PARK (PTY) LTD.

TECHNICAL MEMORANDUM Preliminary Solar Siting Study for the Island of Guam

Automation, Protection, and Control General Engineering Services for JEA Generating Plants and Substations

INVENERGY LLC Meeting Summary Report Northline Solar Project

Powered by Safety. Powell Training Catalog

TOLEDO METROPOLITAN AREA COUNCIL OF GOVERNMENTS

Request for Proposal

GESP Procurement Plan MARCH 2017

Solar Electricity For Community Buildings Pilot Program. Workbook

UK Universities Student Sensor Competition

WC-OSH 109 Tagging and Isolation

PROCUREMENT PLAN. Procurement of Goods and Works Method Threshold Comments. Consulting Services

Transcription:

Generator Interconnection Facilities Study Report Franklin County, NC 50.0 MW Solar Farm Queue #384

Table of Contents 1 PURPOSE... 3 2 ASSUMPTIONS... 3 3 RESULTS... 4 3.1 Power-flow Analysis Results... 4 3.2 Stability Analysis Results... 4 3.3 Power Factor Requirements... 5 3.4 Short Circuit Analysis Results... 6 3.5 Harmonics Assessment... 6 3.6 Interconnection of Customer s Generation... 6 3.7 Estimate of Interconnection Cost... 7 4 SUMMARY... 8 APPENDIX I : FIGURES... 9-2 -

1 PURPOSE The purpose of this Facilities Study is to assess the impacts of the generator interconnection requests on the reliability of the (DEP) transmission system with respect to power flow, power factor, stability, and short circuit. Estimates of the cost and time required to interconnect the generation as well as to resolve the impacts as determined in this analysis are also included. The DEP internal system analysis consists of an evaluation of the internal DEP transmission system utilizing documented transmission planning criteria. The request is described in Table 1 below. DEP Generator Interconnection Queue No. MW Table 1: Interconnection Requests Requested In-Service Date County Interconnection Facility 384 50.0 6/30/2018 Franklin County, NC Franklinton-Spring Hope SS 115 kv Line 2 ASSUMPTIONS The following Facilities Study results are from the DEP internal power-flow models that reflect specific conditions of the DEP system at points in time consistent with the generator interconnection requests being evaluated. The cases include the most recent information for load, generation, transmission, interchange, and other pertinent data necessary for analysis. Future years may include transmission, generation, and interchange modifications that are not budgeted and for which no firm commitments have been made. Further, DEP retains the right to make modifications to modeling cases as needed if additional information is available or if specific scenarios necessitate changes. For the systems surrounding DEP, data is based on the ERAG MMWG model. The suitability of the model for use by others is the sole responsibility of the user. Prior queued generator interconnection requests were considered in this analysis. The results of this analysis are based on Interconnection Customer s queue requests including generation equipment data provided. If the facility technical data or interconnection points to the transmission system change, the results of this analysis may need to be reevaluated. This study was based on the following assumptions: CUSTOMER would construct, own and operate the electrical infrastructure that would connect their generation to DEP s facilities, including any step up transformers and lines from the generators, but excluding the circuit breaker in the new breaker station where applicable. - 3 -

3 RESULTS 3.1 Power-flow Analysis Results Facilities that may require upgrade within the first three to five years following the in-service date are identified. Based on projected load growth on the DEP transmission system, facilities of concern are those with post-contingency loadings of 95% or greater of their thermal rating and low voltage of 92% and below, for the requested in-service year or the in-service year of a higher queued request. The identification of these facilities is crucial due to the construction lead times necessary for certain system upgrades. This process will ensure that appropriate focus is given to these problem areas to investigate whether construction of upgrade projects is achievable to accommodate the requested interconnection service. All queue requests, as well as nearby existing and prior-queued generation, were modeled and assumed to be operating at full output. Contingency analysis study results show that interconnection of these generation facilities result in NO potential thermal or voltage issues on the DEP system. 3.2 Stability Analysis Results A stability analysis was performed to determine the impact of the proposed generation additions on the DEP transmission system and other nearby generation. All queue requests, as well as nearby existing and prior-queued generation, were modeled and assumed to be operating at full output. The proposed solar farm was modeled considering the specific layout and number of inverters (20 SMA 2750-EV-US, 55 MVA). The model included a single lumped equivalent generator (to represent the inverters) with inverter transformer (5.75%Z at 2750 kva x 20) and collector impedance. The interconnection to the DEP transmission system was via a single substation transformer (6.5%Z at 33.1 MVA base), based on data provided by the Customer. A representative set of faults was simulated to determine if there would be any adverse impact to the transmission system as a result of the proposed generation. The ability of the solar farm to ride through the voltage depressions resulting from the faults was also verified, based on the model parameters provided by the Customer. The stability evaluation did NOT identify any stability related problems. All generators stayed on-line and stable for all simulated faults. If the Customer data changes from that provided, these results will need to be reevaluated. - 4 -

3.3 Power Factor Requirements DEP s Large Generator Interconnection Procedure (LGIP) requires the proposed generation to be capable of delivering the requested MW to the Point of Interconnection (POI) at a 0.95 lagging power factor. For analysis of the power factor requirement, the Customer-supplied data regarding inverter capabilities, collector field configuration, impedances and line charging, and transformer impedances were used. The results of the analysis indicate that the proposed solar plant design, without capacitors, DOES NOT meet the 0.95 lagging power factor requirement at the POI for the requested MW delivery level. The requester has indicated that they will NOT add a capacitor bank to the design. If a capacitor bank is NOT included in the plant design, Table 2 below summarizes the approved MW at the POI, along with the MVAR capability at the POI required to meet the 0.95 lagging power factor requirement at the POI. Table 2: MW Approved and MVAR Capability Required at the POI to Meet Power Factor Requirements Reduce MW Option DEP Generator Interconnection Queue No. MW Requested MW Approved MVAR Capability Required 384 50.0 48.7 16.1-5 -

3.4 Short Circuit Analysis Results A short circuit analysis was performed to assess the impact of the proposed generation addition on transmission system equipment capabilities. The analysis indicates that no short circuit equipment capabilities will be exceeded as result from the proposed generation additions and associated transmission upgrades. The results of the short circuit study are based on Customer provided generation equipment data and location. Also, the prudent use of engineering assumptions and typical values for some data were used. If the units technical data or interconnection points to the transmission system changes, the results of this analysis may need to be reevaluated. 3.5 Harmonics Assessment There is potential interaction of harmonic current injections from the Customer s proposed generation and certain capacitor banks on the DEP system. Testing may be necessary after the actual in-service date of this generation and the Customer will be responsible for mitigation of any detrimental impacts to the system. 3.6 Interconnection of Customer s Generation The point of interconnection for Queue #384 is a new 115 kv breaker station connected to the Franklinton-Spring Hope SS 115 kv Line near structure 286. The breaker station one-line is provided as Figure 1. The customer should verify that the MVA ratings of their connecting lines are sufficient to accommodate delivering the total MVA output to the point of interconnection at the required 0.95 power factor. - 6 -

3.7 Estimate of Interconnection Cost Q384 The estimate includes the assumption that DEP will acquire and use a portion of the property that the Customer will secure for the addition of the facility. Tap Line Description: Estimated Cost: $1,000,000 New Breaker Station Description: Estimated Cost: $2,400,000 DEP will tap the Franklinton-Spring Hope SS 115 kv Line and Construct a short tap line to New Breaker Station adjacent to DEP ROW. Manual switches will be installed on each side of the Tap. Construct new 1-230 kv breaker station at generation new connection point. Assumes a control building with cable trench, line trap, CCVTs, surge arrestors, power pot, 230 kv breaker with air break switches, metering PTs and CTs. Install Transfer Trip Scheme at New Breaker Station and Transmission Substations Description: It will be necessary to separate this generation facility from the DEP system for faults on the Franklinton-Spring Hope SS 115 kv Line. Install protection system and transfer trip for coordination between the above listed transmission line and proposed generation facility. Estimated Cost: $350,000 Taxes Description: NC utility tax of 7% Estimated Cost: $262,500 Total Interconnection Cost Estimate: $4,012,500-7 -

APPENDIX I : FIGURES Figure 1- - 9 -