TRIP OF YALLOURN POWER STATION NO KV BUSBAR ON 6 DECEMBER 2015

Similar documents
NATIONAL NUCLEAR REGULATOR

Generator Interconnection System Impact Study Report Carteret County, NC MW Queue #297 Original Submittal Revision 1

CREDIT LIMIT PROCEDURES: APPLICATION OF OFFSETS IN THE PRUDENTIAL MARGIN CALCULATION CONSULTATION FINAL REPORT AND DETERMINATION

Application form for Commissioning Generation Facility Registration by a Market Participant. including explanatory notes

XXXXX Kwalsa Phase II Project. Interconnection Facilities Study and Project Plan

Our Terms of Use and other areas of our Sites provide guidelines ("Guidelines") and rules and regulations ("Rules") in connection with OUEBB.

Inspection and Testing of Signalling - Roles, Responsibilities & Authorities

Addendum 1 Compliance indicators for the Australian Privacy Principles

Generator Interconnection Facilities Study Report Franklin County, NC 50.0 MW Solar Farm Queue #384

RG 102 Accreditation for the Inspection of Non-public High Voltage Electrical Systems

MOS ESTIMATES REPORT: MOS PERIODS; MARCH 2015, APRIL 2015 & MAY 2015

Life Extension of Nuclear Power Plants

A. General provisions and other electrical systems are specified in other Sections of Division 26.

SUP 08 Operational procedures for Medical Gas Pipeline Systems (MGPS) Unified procedures for use within NHS Scotland

Advance Care Planning: Getting started

1.4 On 19 May 2011 the WA State Government announced a reduction in the Subsidy rate from 40c/kWh to 20c/kWh effective from 1 July 2011.

Bharat Heavy Electricals Limited (A Government of India Undertaking)

Business Process Human Research Ethics Application and Review System

Registering your business name

ELECTRICAL INSPECTION ACT CANADIAN ELECTRICAL CODE REGULATIONS

2016 National MAX Indigenous Art Competition

Client name:... Billing name:... Address:... address:... ABN/ACN:... Contact name:... Phone number:... Cost register (office use):...

Requirements of the Civil Aviation Authority of Thailand

The University of Texas at San Antonio

12d Synergy and 12d Model

SOUTH AFRICAN NATIONAL STANDARD

Client name:... Billing name:... Address:... address:... ABN/ACN:... Contact name:... Phone number:... Cost register (office use):...

Generator Interconnection Impact Study Report Bladen County, NC 75.0 MW Solar Farm Queue #377

LOCAL SPORT DEFIBRILLATOR GRANT PROGRAM GUIDELINES OPENING: 1 NOVEMBER 2017 CLOSING: 20 DECEMBER 2017

Dodo Power & Gas. Customer Hardship Policy

SEEK EI, February Commentary

Australia s National Guidelines and Procedures for Approving Participation in Joint Implementation Projects

The Assessment of Postoperative Vital Signs: Clinical Effectiveness and Guidelines

Marina Strategy: Section A Request for Proposal. 1. Request for Proposal. 2. Communication. 3. Key Contacts

Small Business Entrepreneur Grants Program

PAKISTAN CIVIL AVIATION AUTHORITY REQUEST FOR PROPOSAL ENERGY PERFORMANCE CONTRACT AT JINNAH INTERNATIONAL AIRPORT

National Footy Facilities Fund. Guidelines

Marine Protection Rules Part 130B Oil Transfer Site Marine Oil Spill Contingency Plans

JOB ADVERTISING STRENGTHENING SHARPLY IN MINING STATES AND TENTATIVELY STABILISING IN NON-MINING REGIONS, REDUCING NEED FOR

THE CITY OF SEATTLE CITY LIGHT DEPARTMENT 2012 REQUEST FOR PROPOSALS. Long-Term Renewable Resources And/or Renewable Energy Certificates

Freelancer launches API

UNIFIED FACILITIES GUIDE SPECIFICATIONS

QP29.20 Revision 15 Safety

COMMUNITY GRANTS PROGRAM GUIDELINES & TERMS & CONDITIONS

professional PRACTICE

THE PRIVACY ACT AND THE AUSTRALIAN PRIVACY PRINCIPLES FREQUENTLY ASKED QUESTIONS

australian nursing federation

ATTACHMENT B. 1. Intent to Bid/Bidder Contact Information Form. 2. Executive Summary. 3. Proposal Characteristics and Term Sheet

COMDTPUB P16721 NVIC August 25, 2014

Outage dates (duration): September 5, 1996 to May 27, 1999 (2.7 years) Reactor age when outage began: 8.8 years

THE MICROSOFT Cloud Society Master of the Month CONTEST ( Contest ) Terms and Conditions ( Terms and Conditions )

BP HUSKY TOLEDO REFINERY

107 FERC 61,053 UNITED STATES OF AMERICA FEDERAL ENERGY REGULATORY COMMISSION

WECC Criterion PRC-006-WECC-CRT-3

AUSTIN ENERGY REQUEST FOR PROPOSALS (RFP) FOR THE PURCHASE OF RENEWABLE CAPACITY & ENERGY FROM RENEWABLE ENERGY RESOURCES

Rules Australian STEM Video Game Challenge 2016

Invitation to Submit Expression of Interest and Proposal

Generator Interconnection Impact Study Report Wayne County, NC 20.0 MW Solar Farm Queue #364

Scottish Health Technical Memorandum Electrical safety guidance for low voltage systems

COMPLIANCE WITH THIS PUBLICATION IS MANDATORY

The Try, Test and Learn Fund: At-risk young people aged and receiving income support

The Narragansett Electric Company d/b/a National Grid

QRI SCHOLARSHIPS Major Academic Award

GDPR DATA PROCESSING ADDENDUM. (Revision March 2018)

STATE OF NORTH CAROLINA UTILITIES COMMISSION RALEIGH DOCKET NO. E-2, SUB 1089 BEFORE THE NORTH CAROLINA UTILITIES COMMISSION

Thank you for the opportunity to present submissions to the inquiry into Charity Fundraising in the 21 st Century.

Contact for follow up Abigail Powell, Senior Research Fellow, Centre for Social Impact: Ph:

Service Line: Rapid Response Service Version: 1.0 Publication Date: June 22, 2017 Report Length: 5 Pages

New England Telehealth Consortium

Interim Australian/New Zealand Standard

Fundraising Guidelines. & Application

2.3. Any amendment to the present "Terms and Conditions" will only be valid if approved, in writing, by the Agency.

Work of Internal Auditors

NRC INSPECTION MANUAL STSB

COMMUNITY GRANTS PROGRAM GUIDELINES & TERMS & CONDITIONS

Nations will be notified of the result of their applications by return by September 18 th.

PART A. In order to achieve its objectives, this Code embodies a number of functional requirements. These include, but are not limited to:

GAO INDUSTRIAL SECURITY. DOD Cannot Provide Adequate Assurances That Its Oversight Ensures the Protection of Classified Information

[PDF] STAR DELTA STARTER THEORY ARCHIVE

Partnerships Scheme. Call for Proposals

MRT Registration. Contact details

Essential Conditions and Standards for Continuing Registration

If any queries arise ESB Networks DAC can be contacted at or

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

UNITED STATES OF AMERICA BEFORE THE FEDERAL ENERGY REGULATORY COMMISSION ) ) )

Pershing International Securities Trading Terms and Conditions

TABLE OF CONTENTS. Assistance offered by The Leila Rose Foundation. Guidelines for Assistance. LRF Privacy Policy. Patient Advocate Disclaimer

NeoOne VPN Service Specific Terms and Conditions

Topic 3 Contribute to safe work practices in the workplace 43

INFORMATION BULLETIN OPERATING PERMITS

Notre Dame College Website Terms of Use

Tearfund Risk Assessment Guidelines

PER-005 System Personnel Training

Retention and Disposal Authority for Records of the Accredited Training Function

For further information or support please contact the QTIC team on (07) or

HUMAN FACTORS ENGINEERING - VALVES

Engineering Waiver Management

Standard NUC Nuclear Plant Interface Coordination

Final Report. Apple and Pear Nuffield Scholarship 2014/2015. Annie Farrow Apple & Pear Australia Limited (APAL) Project Number: AP13034

REGISTRATION FOR HOME SCHOOLING

Transcription:

TRIP OF YALLOURN POWER STATION NO.2 220 KV BUSBAR ON 6 DECEMBER 2015 AN AEMO POWER SYSTEM OPERATING INCIDENT REPORT FOR THE NATIONAL ELECTRICITY MARKET Published: March 2016

VERSION RELEASE HISTORY VERSION DATE BY CHANGES CHECKED BY AUTHORISED BY 1 17 Mar 2016 N Modi Initial P Biddle M.Stedwell INCIDENT CLASSIFICATIONS Classification Detail Time and date of incident 2157 hrs Sunday 6 December 2015 Region of incident Victoria Affected regions Victoria Event type Busbar trip (BB) Generation Impact 732 MW of generation was disconnected as a result of this incident Customer Load Impact No customer load was disconnected as a result of this incident Associated reports Nil ABBREVIATIONS Abbreviation AEMO CB kv MW NER No.2 Line No.2 Busbar No. 8 Line YPS YWPS Term Australian Energy Market Operator Circuit Breaker Kilovolt Megawatt National Electricity Rules Yallourn to Hazelwood No.2 220kV transmission line YTS No.2 220kV busbar Yallourn to Rowville No.8 220kV transmission line Yallourn Power Station switchyard Yallourn West Power Station 2015. The material in this publication may be used in accordance with the copyright permissions on AEMO s website. Australian Energy Market Operator Ltd ABN 94 072 010 327 www.aemo.com.au info@aemo.com.au NEW SOUTH WALES QUEENSLAND SOUTH AUSTRALIA VICTORIA AUSTRALIAN CAPITAL TERRITORY TASMANIA

IMPORTANT NOTICE Purpose AEMO has prepared this document to provide information about this particular Power System Operating Incident. Disclaimer This document or the information in it may be subsequently updated or amended. This document does not constitute legal or business advice, and should not be relied on as a substitute for obtaining detailed advice about the National Electricity Law, the National Electricity Rules, or any other applicable laws, procedures or policies. AEMO has made every effort to ensure the quality of the information in this document but cannot guarantee its accuracy or completeness. Accordingly, to the maximum extent permitted by law, AEMO and its officers, employees and consultants involved in the preparation of this document: make no representation or warranty, express or implied, as to the currency, accuracy, reliability or completeness of the information in this document; and are not liable (whether by reason of negligence or otherwise) for any statements or representations in this document, or any omissions from it, or for any use or reliance on the information in it. Copyright 2016. Australian Energy Market Operator Limited. The material in this publication may be used in accordance with the copyright permissions on AEMO s website. 2015. The material in this publication may be used in accordance with the copyright permissions on AEMO s website. Australian Energy Market Operator Ltd ABN 94 072 010 327 www.aemo.com.au info@aemo.com.au NEW SOUTH WALES QUEENSLAND SOUTH AUSTRALIA VICTORIA AUSTRALIAN CAPITAL TERRITORY TASMANIA

1. OVERVIEW This report reviews a power system operating incident that occurred on 6 December 2015 at Yallourn Power Station (YPS) switchyard in Victoria. This incident involved the trip of a 220 kv bus bar and Yallourn West Power Station (YWPS) generating units 1 and 2. There was no loss of customer load as a result of this incident. AEMO is required to assess power system security over the course of this incident as the incident was a non-credible contingency event 1 under the National Electricity Rules (NER). 2 Specifically, AEMO is required to assess the adequacy of the provision and response of facilities and services and the appropriateness of actions taken to restore or maintain power system security. 3 For this incident AEMO concluded that: 1. The incident was initiated by a circuit breaker (CB) at YPS that did not open correctly, resulting in the trip of a busbar at YPS and two generating units at YWPS. 2. Power system security was maintained over the course of the incident. This report is based on information provided by AusNet Services 4, EnergyAustralia 5 and AEMO. National Electricity Market time (Australian Eastern Standard Time) is used in this report. 2. THE INCIDENT On Sunday, 6 December 2015 at 2157 hrs, the YPS No.2 220kV busbar (No.2 busbar) and YWPS generating unit 2 tripped. At the time YWPS generating unit 3 was being taken out of service. As a consequence of the busbar trip, the Yallourn to Rowville No.8 220kV transmission line (No. 8 Line) was offloaded. Three minutes later, at 2200 hrs, YWPS generating unit 1 also tripped, offloading the Yallourn to Hazelwood No.2 220kV transmission line (No.2 Line). As a result of this incident 732 MW of generation was lost, however there was no loss of customer load. The minimum frequency during this event was 49.75Hz and the frequency operating standards were not exceeded. No.2 busbar, No.8 Line and No.2 Line were returned to service by 2347 hrs the same day. See Appendix A for a power system diagram illustrating the incident and Appendix B for a chronological log of the incident. The reason for investigating this incident is that a busbar trip is a non-credible contingency event. The probability of a busbar fault is very low and is thereby an unexpected event known in power system security terms as a non-credible contingency event. 6 1 The power system is operated such that it will remain in a satisfactory operating state (NER clause 4.2.2) for the loss of single elements in the transmission network. Such events are defined as credible contingency events (NER clause 4.2.3). AEMO considers the occurrence of these events to be reasonably possible and ensures contingency plans are in place to minimise the impact on the power system following a credible contingency event. A non-credible contingency event is a contingency event other than a credible contingency event and usually involves multiple elements. 2 NER Clause 4.8.15(a)(1)(i) and AEMC Reliability Panel Guidelines for Identifying Reviewable Operating Incidents. 3 NER Clause 4.8.15(b) 4 Information provided by AusNet Services has been provided on a without prejudice basis and nothing in this report is intended to constitute, or may be taken by any person as constituting, an admission of fault, liability, wrongdoing, negligence, bad faith or the like on behalf of AusNet Services (or its respective associated companies, businesses, partners, directors, officers or employees). 5 EnergyAustralia is the operator of Yallourn Power Station 6 NER Clause 4.2.3 - Credible and non-credible contingency events; AEMO Power System Security Guidelines, Section 10 - Definition of a noncredible contingency events AEMO 2014 4

3. AUSNET SERVICES INVESTIGATION AusNet Services, as owner of the 220kV busbars and associated switchgear at YPS, investigated this incident and have provided the following information. At 2157hrs 6 December 2015, the YPS No.2 220kV busbar tripped via protection. At the time of this event, YWPS operators were in the process of shutting down unit 3. Inspection of station apparatus and protection targets at YPS indicated that one phase of the Yallourn 3 Generator 2B 220kV CB did not open correctly in response to a trip signal from the Power Station. This resulted in operation of the CB fail protection tripping the YPS No.2 220KV busbar. This is an expected outcome for this type of fault. The busbar outage resulted in the offloading of the Yallourn Rowville No.8 220kV line and the YWPS A and D auxiliary transformers. YWPS unit 2 was also islanded. The No.2 220KV bus and the Yallourn Rowville No.8 line were returned to service at 2343hrs. The D and A auxiliary transformers were returned to service at 2359 hrs and 0008 hrs respectively. The YPS 3 Generator No2 bus CB was isolated for repairs and returned to service on 7 December. 4. ENERGYAUSTRALIA INVESTIGATION EnergyAustralia, as operator of YWPS, investigated this incident and has provided the following information. On Sunday 6 December 2015, Yallourn unit 3 was being taken out of service for a controlled shutdown. When a turbine trip was initiated at 13 MW, an open command was sent to both the Unit 3 YPS No1 220kV busbar CB and the Unit 3 YPS No2 220kV busbar CB. This resulted in the unexpected trip of the No2 220KV busbar at YPS. At the time, YWPS Unit 2 was online and generating 382 MW. As a result of the No.2 Busbar trip, YWPS Unit 2 was islanded and subsequently tripped. About three minutes after the No.2 220KV busbar trip, YWPS unit 1 ran back from 350MW and tripped due to loss of auxiliary supplies as a result of the trip of the YPS No.2 220kB busbar. At the time of the incident, the auxiliary supplies for YWPS unit 1 were being fed via auxiliary transformer A, which is connected to the YPS No.2 220KV busbar. Auxiliary transformer B fed from the YPS No.1 220KV bus was out of service at the time of the incident. Auxiliary supplies normally fed from the B transformer were being fed from auxiliary transformer C. Appendix A shows the 220KV connections of the YWPS auxiliary supply transformers. When auxiliary transformer A tripped, there would normally be an automatic changeover to auxiliary transformer C. However, this did not happen as auxiliary transformer C was already supplying the loads normally supplied by auxiliary transformer B and the auto-changeover was blocked. While a manual change-over facility is available, this was not used as the station operators were unable to find the interlock bypass facility to enable them to override the auto-changeover block. This is because it was not located on the operator control screens like other interlocks. EnergyAustralia has subsequently modified its control screens to include the interlock by-pass facility. AEMO 2014 5

5. POWER SYSTEM SECURITY AEMO is responsible for power system security in the NEM. This means AEMO is required to operate the power system in a secure operating state and return the power system to a secure operating state following a contingency event. This section assesses how AEMO managed how power system security over the course of this incident 7. To ensure the power system was returned to and maintained in a secure operating state 8 AEMO invoked constraint sets V-YP_BUS2 9, V-ROYP78_R 10 and V-HWYP2 11 within an acceptable 13 minutes of the incident. No further actions were required to maintain power system security. 5.1 Reclassification In accordance with clause 4.2.3A of the NER, AEMO considered whether to reclassify this non-credible contingency event as a credible contingency event. As the cause of the contingency was known, AEMO was satisfied that the non-credible contingency event was unlikely to re-occur, and so did not reclassify it as a credible contingency event. For this incident, AEMO took appropriate action to ensure the power system returned to a secure operating state following the No.2 Busbar trip. No further action was required to maintain power system security. 6. MARKET INFORMATION AEMO is required by the NER to inform the market about incidents as they progress. This section assesses how AEMO informed the market 12 over the course of this incident. AEMO issued three market notices in relation to this incident: 1. At 2308hrs AEMO issued market notice 50843 to advise the market of the occurrence of the non-credible contingency event and the constraint sets invoked. 2. At 2334hrs AEMO issued market notice 50844 as a correction to market notice 50843 (incorrect date in the original market notice) 3. At 0012hrs AEMO issued market notice 50845 to advise the cause of the non-credible contingency event had been identified and that the contingency would not be reclassified. Over the course of this incident AEMO issued appropriate, timely and sufficiently detailed market information. 7 AEMO is responsible for power system security in the NEM and is required to operate the power system in a secure operating state (NER Clause 4.2.4 (a)). AEMO must thereby ensure that the power system is maintained in, or returned to, a secure operating state following a contingency event. 8 AEMO is required to return the power system to a secure state within thirty minutes following a contingency event - NER Clause 4.2.6 (b) 9 Outage of Yallourn PS No2 220KV Bus 10 Outage of Yallourn to Rowville No7 or No 8 220KV line. 11 Outage of Yallourn to Hazelwood No2 220KV line 12 AEMO generally informs the market about operating incidents as the progress by issuing Market Notices see AEMO website AEMO 2014 6

7. CONCLUSIONS AEMO concluded that: 1. The Yallourn Power Station No. 2 220KV busbar tripped when a circuit breaker failed to open correctly. 2. Yallourn Power Station unit 1 tripped due to loss of auxiliary supplies associated with the trip of the No.2 220KV busbar. 3. The provision and response of facilities and services were appropriate and power system security was maintained over the course of the incident The are no outstanding issues to resolve as a result of this incident. AEMO 2014 7

APPENDIX A. POWER SYSTEM DIAGRAM The power system immediately after the incident YALLOURN (Part) ROTS 8 ROTS 7 2 1 ROTS 6 ROTS 5 W4 W3 W2 HWPS 1 W1 DTR NO NO NO HWPS 2 ETR A S/S Trans C S/S Trans B S/S Trans 220 kv Busbar, line Out of service Busbar, line 2 Winding Tap Transformer 2 Winding Transformer Closed Circuit Breaker Open Circuit Breaker NO Normally Open Circuit Breaker AEMO 2014 8

APPENDIX B. INCIDENT EVENT LOG Chronological Log of Incident Time and Date Event 21:56 6 December 2015 YWPS Unit 3 preparing to come off line. 21:57 6 December 2015 YPS No.2 220kV bus, YWPS Unit 2 and Yallourn PS Auxiliary transformers A, & D tripped. Yallourn to Rowville No.8 220kV line offloaded 22:00 6 December 2015 YWPS Unit 1 tripped. Yallourn to Hazelwood No.2 220kV line offloaded. 22:05 6 December 2015 Constraint Sets V-YP_BUS2 and V-ROYP78_R invoked. 22:10 6 December 2015 Constraint Set V-HWYP2 invoked. 23:43 6 December 2015 YPS No.2 220kV bus and Yallourn to Rowville No.8 220kV line returned to service. 23:47 6 December 2015 Yallourn to Hazelwood No.2 220kV line returned to service. 00:10 7 December 2015 Constraint Sets V-YP_BUS2, V-ROYP78_R and V-HWYP2 revoked. AEMO 2014 9