Document o. 58718 Easylink to iebert Sitelink Module PRODUCT DESCRIPTIO The Easylink Module mounts in an enclosure (P/ 58700, 115 Vac or P/ 58795, 0 Vac). Once installed, the Easylink Module is positioned approximately 1/4 inches off the back wall of the enclosure on a board bracket and four standoffs. There are two manmachine interface () ports on the Module the and the MODEM. These ports are RS ports with quickconnect RJ11 jacks. OTE: All circuits are supervised, except for the MODEM and ports. The Memory Board, which is located underneath the Memory Board cover, plugs into the Easylink Board and contains the iebert Sitelink module firmware (readonly memory (ROM)). Power is supplied to the Easylink Board via a 1 Vdc plugin power supply (P/ 5451, 115 Vac or 54516, 0 Vac). OTE: Refer to the Easylink to iebert Sitelink Technical Manual (5874) for further information about the system installation and programming constraints. PRODUCT UMBERS 58768 Easylink to iebert Sitelink module 5451 Controller Plugin Power Supply, 115 Vac 54516 Controller Plugin Power Supply, 0 Vac 545710 Battery Replacement Kit. Refer to 545408 ISTAATIO COVETIOS CAUTIO: Equipment damage, or loss of data may occur if the you do not follow the procedure as specified. REQUIRED TOOS AD MATERIAS Electrostatic discharge (ESD) wrist strap latblade screwdriver (1/8inch blade width) Wire strippers or each older iebert Sitelink, one RS to RS485 converter is required. Use only Black Box Corporation P/ IC109AR (115 Vac), P/ IC109AE (0 Vac) OR iebert REPOPT. Trunk Interface II will not work. The interface is not required with Sitelink 4 or Sitelink 1. One 115V or 0V (depending on device) receptacle per sitelink to power the Black Box or iebert REPOPT. Cabling and connectors (igure 7 or igure 8). PREREQUISITES CAUTIO: Always wear an electrostatic discharge wrist strip and discharge accumulated static before touching field panel components. Easylink enclosure installed (see Installation Instructions P/ 58701). All conduit runs to enclosure complete. Staefa and iebert systems installed and checked out by certified representatives for each system. These checkouts must confirm that each system is operating and ready to communicate with the other system. Communication network wire runs from dedicated Staefa et Controller Trunk to Easylink with wire leads stripped and mating connector available. All required tools and prerequisites from iebert system completed. Page 1 of 7
Document o. 58718 EXPECTED ISTAATIO TIME 15 minutes VOTAGE, CURRET RATIGS B, Trunk, /Modem Port RS485 Standard RS Standard MEMORY BOARD COTROER BOARD PORT Underwriters aboratories Inc. ISTED C SMOKE COTRO SYSTEM EQUIPMET SUBASSEMBY. Also suitable for use as: EERGY MAAGEMET SUBASSEMBY. Also suitable for use as: SIGA SYSTEM UIT SUBASSEMBY. Also suitable for use as: PROCESS MAAGEMET EQUIPMET SUBASSEMBY. Issue o. or use with System 600 as part of an engineered smoke control system in accordance with PA 9A. WARIG: Power must be O when replacing the battery, otherwise the cabinet will coldstart. WARIG: Risk of static discharge. Turn O power before removing or servicing boards. Use ESD wrist strap when servicing unit. Controller Board B # ield Panel o./ame Memory 1 BPS (Bits per second) Modem B TIU Enabled Port Modem Port Adhere Bar Code abel in this space. JP O 1 O 0 MODEM PORT GROUDIG SPADE POWER SWITCH 1 VDC BATTERY TX 1 B TX B STATUS BATT OW GW0454R1 1 S S S S B THIRD PARTY COECTOR STAEA SYSTEM COECTOR igure 1. Easylink Controller Module. ISTRUCTIOS Preparing to Install the Easylink Board CAUTIO: Before removing or installing the Easylink Board, ensure that the power is shut O on the board (igure 1). 1. Place the electrostatic discharge (ESD) wrist strap on your wrist and attach it to a good earth ground.. Remove the temporary connector cover that is wrapped around the board bracket (igure ). igure. Temporary Cover.. Unpack the Easylink Module from the antistatic bag. Page of 7
Document o. 58718 Installing the Easylink Board BOARD BRACKET WITH STADOS CAUTIO: Improperly aligning and/or installing the board may damage it. WIRE COVER 6. Plug the grounding strap wire into the grounding spade labeled JP on the Easylink Module (igure 1). 7. Remove the and B connectors from the temporary cover. Reserve for later use. 8. Discard the temporary connector cover. Connecting Easylink to Staefa et Controller Trunk GW0509R1 ETWORK COECTORS ITERATURE POCKET RECEPTACES (115 VAC SHOW) 1. Connect the Easylink B Port and Staefa et Controller Trunk using the guidelines in igure 7.. Move the TT/485 switch to the RS485 position for the Staefa et Controller trunk that is dedicated to Easylink (igure 5). igure. Easylink Enclosure Inside View. 1. Rotate the top two plastic standoffs on the board bracket so that the clip of the standoff is positioned at the top. (igure ). TT TRUK C00R1 RS485 igure 4. Module Installation.. With the EDs and connectors facing you, slide the bottom of the board at a 10 angle into the bottom guides on the board bracket (igure 4).. Position the Module over the standoffs. 4. Straighten the grounding strap so that the spade connector is not behind the Easylink bracket. 5. Push the Module cover back until each standoff snaps into position. GW0481R1 TO EASYIK B PORT igure 5. Staefa et Controller TT/485 Switch. Page of 7
Document o. 58718 Connecting Easylink to iebert Sitelink System There are three methods of connecting Easylink to iebert Sitelink System: Sitelink4 or Sitelink1 direct connection Sitelink DC 4i or SitelinkDC 1i using Black Box Device Sitelink DC 4i or SitelinkDC 1i using REPOPT ollow the corresponding steps to connect the Easylink to the iebert Sitelink System: Sitelink4 or Sitelink1 direct connection 1. Make cables per diagram in igure 6.. Connect cables per diagram in igure 6. RS485 TRUK STAEA ET COTROER S B 1 EASYIK RS485 TRUK CABE (MAX 500' / 1066.8 m; STADARD 4 AWG OW CAPACITACE) 1 4 5 COMMUICATIO PORT A SITEIK4 OR SITEIK1 GW0544R COECTIOS TO IEBERT DEVICES 11 igure 6. Easylink Connection to iebert System Using Sitelink4 or Sitelink1. Page 4 of 7
Document o. 58718 Sitelink DC 4i or SitelinkDC 1i using Black Box Device 1. Configure Black Box switches per Table 1. OTE: When using multiple Black Boxes, switch S of the Black Box furthest from the Easylink Enclosure (assuming series connection) will be on. All other S switches will be off.. Make cables per diagram in igure 7. OTE: With the IC109AR (115 Vac), you can use the RS cable provided by the Black Box if the cabling does not need to pass through conduit. A 9pin (male) gender changer is required. Table 1. IC109AR Switch Settings. Switch ID Setting XW1B DTE W8 BC W15 BC W5 AB W9 C W17 C W16 B S1 Out S On* S Off. Connect cables per diagram in igure 7. RS485 TRUK STAEA ET COTROER S B 1 EASYIK RS485 TRUK CABE (MAX 500' / 1066.8 m; STADARD 4 AWG OW CAPACITACE) TO OTHER BACK BOX/SITEIK COMBIATIOS POWER PACK POWER PACK POWER BACK BOX POWER BACK BOX TXA TXB A B TAPE BACK SHIED RS PORT (5PI EMAE) 7 TXA TXB A B RS PORT (5PI EMAE) 7 5 5 RS PORT (9PI MAE) RS PORT (9PI MAE) GW0478R IEBERT SITEIK IEBERT SITEIK igure 7. Easylink Connection to iebert System Using a Black Box Device. Page 5 of 7
Document o. 58718 Sitelink DC 4i or SitelinkDC 1i using REPOPT 1. Set ET A Select to RS.. Make cables per diagram in igure 8.. Connect cables per diagram in igure 8. RS485 TRUK STAEA ET COTROER S B 1 EASYIK TO OTHER REPOPT/SITEIK COMBIATIOS IEBERT REPOPT ET A RS (9 PI) ET B RS485 5PI MAE PORT 7 ET A SEECT 485 IEBERT REPOPT ET A RS (9 PI) ET A SEECT 485 ET B RS485 5PI MAE PORT 7 IEBERT SITEIK IEBERT SITEIK GW047R 5 PORT B (9PI MAE) Wiring specified by iebert. Confirm wiring terminations with local representative. 5 PORT B (9PI MAE) igure 8. Easylink Connection Using REPOPT. Page 6 of 7
1 B Document o. 58718 POWERIG THE EASYIK TO IEBERT ollow these steps to connect power to the Easylink: 1. Insert the DI plug into the DI socket labeled 1 Vdc on the Easylink Module (igure 9). 1 VDC S S S S 1 VDC COECTOR 0019R1 000R1 igure 10. 115 Vac Power Supply Plugged into Power Receptacle.. Switch on power to Easylink (igure 1). OTE: Power is on when EDs on the bottom of the board are lit. 4. Pull the mylar strip off of top of battery (igure 11). igure 9. 1 Vdc Power Supply Connection to Easylink Module. BATTERY SIP. Plug the power pack into the power receptacle of the Easylink Enclosure (igure 10). 004R1 igure 11. Battery with Mylar Slip. The installation is now complete. Information in this publication is based on current specifications. The company reserves the right to make changes in specifications and models as design improvements are introduced. 000,. 1000 Deerfield Parkway Buffalo Grove, I 60089451 U.S.A. Your feedback is important to us. If you have comments about this document, please send them to technical.editor@sbt.siemens.com Document o. 58718 Printed in the U.S.A. Page 7 of 7